Monobloc Outdoor Unit Service Manual
76
Check Code
Determination and action
A
lar
m
[
P
3
44]
C
ur
ren
t A
lar
m
[P
346
] t
o [
P
3
49]
P
a
s
t A
la
rm
[P
350
] t
o [
P
3
54]
Operational Cause
Unit Status
Automatic
Reset
228
33
Inverter high pressure
release failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
detected when discharge pressure exceeds HP switch limit pressure.
1. Check of outdoor fan operation.
2. Check motor error of outdoor fan.
3. Check clogging of outdoor PMV.
4. Check clogging of heat exchanger.
5. Check for re-cycling of air around air heat exchanger
-
50
Exchanger freeze protection
on water temperature (in
cooling)
Stop
X
Automatic reset when EWT or LWT is ≥4°C. Alarm is activated during cooling
mode or a defrost operation and when EWT or LWT < 4°C
Cooler heater is energized while the alarm is active. Water pump is forced to
run.
1.
Check water flow rate
2.
Check water pressure drop
3.
Check EWT sensor
4.
Check LWT sensor
-
51
Exchanger freeze protection
on refrigerant temperature
(in cooling)
Stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Energized
Cooler Heater while alarm is active.
Force pump to run until alarm reset kind becomes manual.
Error becomes definite after retrying operation more than 12 occurrences
within a 2 hours period
1.
Check TR, TD, TS & BP sensors
2.
Check PMV is operating correctly
3.
Check refrigerant circuit for leaks
4.
Check refrigerant pipes are not damaged
243
60
Reversing valve protection
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 4 times.
1. Check operation of 4-way valve.
2. Check air heat exchanger (TE), suction temp. sensor (TS).
3. Check BPHE sensor (TR).
4. Check 4-way valve coil.
5. Check PMV (Pulse Motor Valve).
246
61
Fan error
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit.
Error
becomes definite after retrying operation for 8 times.Error detected in either
of the following condition;
1) Fan motor lock
2) Fan motor IPM over currentat start up
3) Fan IPDU DCvoltage abnormal
Check:
1. Check lock of fan motor.
2. Check power supply voltage between L2 and N.
250
62
Compressor inverter short
circuit protection
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 8 times. Error detected in either
of the following condition;
1) Compressor IPM short circuit
detection at start up
2) Compressor IPM short circuit
detection during coil heating
253
63
Compressor motor position
detection error
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit.
Error
becomes definite after retrying operation for 8 times. Error detected when
offset voltage of motor current sensor is abnormal before compressor start
up.
129
64
Compressor breakdown
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 8 times. Error detected in either
of the following
condition;
1) Compressor over current
2) Compressor IPM short circuit
3) Compressor motor control failure
Check:
1. Check power supply voltage.
2. Overload operation of refrigerating cycle
130
65
Compressor lock
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 8 times. Error detected in either
of the following condition;
1) Compressor motor lock
2) Compressor motor IPM over current at start up
Check:
1. Trouble of compressor (Lock, etc.): Replace compressor.
2. Wiring error of compressor (Open phase)
132
70
Compressor thermal switch
release failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit.
Error
becomes definite after retrying operation for 10 times.
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check PMV (Pulse Motor Valve).
4. Check broken pipe.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...