Monobloc Outdoor Unit Service Manual
112
10.1.3.7. DHW Status Table
Access type: Read-only (force is possible)
TABLE NAME: DHW_STAT, PIC Table Type: 11H, instance 7
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
201
DHW_MODE
0 to 2
-
-
DHW Mode
1
202
dhw_ovr
-1 to 100
-
-
DHW Override
2
203
dhw_dem
No / Yes
-
-
DHW Demand from Tank
204
dhw_cond
True / False
-
-
DHW Conditions
3
205
DHW_CTLP
20.0 to 60.0
-
°C
DHW Control Point
206
DHW_TT
-40.0 to 115.6
-
°C
DHW Tank Temperature
207
shc_time
xxx
-
min
Current SHC Runtime
208
dhw_time
xxx
-
min
Current DHW Runtime
209
DHW_EXCP
0 to 1440
-
min
DHW Exception Timer
114
DHW_REQ
Open / Close
-
-
DHW Request from Tank
4
115
DHW_PRIO
Open / Close
-
-
DHW Priority Button
4
116
DHW_ANTI
Open / Close
-
-
DHW Anti-Legionella Req.
4
117
SUMM_SW
Open / Close
-
-
Summer Switch
4
210
DHW_VLV
Off / On
-
-
DHW Diverting Valve
5
211
DHW_EHS
Off / On
-
-
DHW Elec Heat Stage
212
DHW_RUN
No / Yes
-
-
DHW Running Status
1. DHW mode
0 = DHW Eco mode
1 = DHW anti-legionella mode
2 = DHW regular mode
2. DHW override
-1 = DHW disabled
0 = DHW Operating
1 = DHW Not Operating (Space Heating / Cooling Mode)
2 = DHW Valve moving
3 = DHW Operating with EHS Only
50 = Heat Mode not allowed
100 = DHW Fail
3. DHW conditions
DHW conditions are met (and the flag is set) if the unit is
not in DHW alarm and one of the following conditions is
true:
● DHW only mode is selected
● Summer mode is active (heat pumps only)
● DHW schedule is active
● DHW priority switch is closed
Note
: The unit is allowed to switch into DHW Mode only
when both “DHW Demand from Tank” [P203] and “DHW
Conditions” [P204] are set to "Yes" / "True".
4. Virtual switches
These switches do not correspond to real Discrete Inputs.
Their statuses are mapped to the DI#5 to 8 customized
(see §3.6.2. General electrical connection on terminal
block X2 )
They can be accessed through JBus Registers regardless
of the General Purpose Switches configuration.
5. DHW Diverting Valve
This is the status of the signal sent to the valve in
accordance with the DHW Valve Type configuration
[P701].
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...