Monobloc Outdoor Unit Service Manual
61
13
Freeze Protection
Alarm #50 or #51 is active and
will be automatically reset (number
of allowed occurrences not
reached) <OR> Variable Speed
Pump configured (Par.804=2) and
Compressor starting sequence on
going (capacity override #5 to #8)
and SST below 0°C <OR> Variable
Speed Pump configured
(Par.804=2) and Capacity override
#58 “Low SST” is active.
Run the pump at 100%
14
Compressor or Inverter
failed
Cool Mode or Heat Mode is
selected, no Electric Backup is
active and a “Compressor Fail”
alarm is active.
Stop the pump
15
DHW Valve moving
DHW Valve is moving back to
Space Heating/Cooling and
Compressor is still running.
Run the pump at DHW configured
speed (Par.710)
16
Water Control Point
reached
Variable Speed pump configured
in Delta Temperature logic
([P566]=1), CTRL_TMP [P052]
reaches CTRL_PNT [P051].
Reduce the Current Delta Temp
Setpoint to avoid the pump speed
to decrease too much.
100
Emergency stop
Alarm 100 is active
Stop the pump
8.3.4. Backup Override [P091]
The following table includes all backup overrides with respect to their priority.
#
Override
Conditions
Action
-1
Backup Disabled
No backup is configured
Do nothing
1
Backup running due to
Heat Pump low
capacity
Heat Mode is requested, warm up
timer is elapsed and setpoint is not
satisfied.
Booster is active
2
Backup running as
booster
EHS1 is configured as booster
[P601]and Heat Mode is
Booster is active
3
Backup running during
Defrost
Defrost is active
Booster is active
4
Backup running due to
Heat Pump failure
Heat Pump cannot run the
compressor due to a failure
Backup is active
5
Backup running due to
low OAT
Heat Pump is not allowed to start
due to low OAT
Backup is active
10
Off-peak
Off-peak is active and an electric
backup is configured
Do not allow electric backup
11
Loadshed
Loadshed is active and an electric
backup is configured
Do not allow electric backup
12
Backup stopped
due to DHW Mode
An Elecrical Backup is configured
and DHW Mode is active
Do not allow electric backup
13
Capacity Limit to
0%
A capacity limit is applied
Do not allow electric backup
14
Summer Mode
Summer Mode is active
Do not allow backup
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...