Monobloc Outdoor Unit Service Manual
51
Related parameters for floor drying mode operation:
Par.No
Description
Range
Default
44
System mode request – (MOD_REQ)
0 ~ 9*
-
401
Heat home set point – (hwoccstp): (°C)
20.0 ~ 60.0
45
595
Floor drying starting set point – (dry_stp): (°C)
20.0 ~ 40.0
20
596
Floor drying warm-up days – (drystep1)
0 ~ 99
3
597
Floor drying ramp-up days – (drystep2)
0 ~ 99
4
598
Floor drying hold-up days – (drystep1)
0 ~ 99
4
*To activate the floor drying mode [P044] must be set to 9
The floor drying control can only be activated from the service access level.
8.2.16. Water Pump logic
The ESTIA Monobloc outdoor unit can be configured for the following hydronic pump options:
•
Unit without internal pump. For this option it is necessary to add an external pump (locally supplied), which can
be controlled by the Monobloc outdoor unit
•
Unit with fixed speed pump
•
Unit with variable speed pump
The type of the hydronic options are Factory options. All parameter settings [P804], required for these options, will be
completed by the Factory before the Monobloc outdoor unit is dispatched.
The main pump can be controlled according to the following operating modes and conditions:
Operating Mode
Conditions
Action
Unit Off
-
Pump is stopped
Anti-sticking override [P563]
Pump is running for 2
minutes every 24 hours
Low OAT or very low OAT override
Pump is running
Unit in Alarm
Flow switch failure (alarm 32)
Pump is stopped
Unit with EHS or
Boiler
EHS is configured and Heat Demand exists
Pump is running
EHS is configured, Heat Satisfied and Pump Logic
= 1 “Always ON”
Pump is running
EHS is configured, Heat Satisfied and Pump Logic
= 2 “Water Sampling”
Pump is running periodically
Boiler is configured and Heat Demand exists
Pump is stopped
Boiler is configured and Heat Satisfied
Pump is stopped
Heating Mode
Heat demand exists
Pump is running
Heat satisfied and Pump Logic = 1 “Always ON”
Pump is running
Heat satisfied and Pump Logic = 2 “Water
Sampling”
Pump is running periodically
Boiler is started (OAT below [P514])
Pump is running (very low
OAT override #6)
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...