Monobloc Outdoor Unit Service Manual
38
•
The operation of the cooling mode is determined by the water temperature measured by the LWT sensor
•
The cooling operation will start when:
[1]
Control Temperature (CTRL_TMP) ≥ Control Point (CTRL_PNT) + Water Cool Hysteresis [P411]
•
The cooling operation will continue until:
[2]
Control Temperature (CTRL_TMP) < Control Point (CTRL_PNT) + (Water Cool Hysteresis [P411]
OR
[3]
Control Temperature (CTRL_TMP) < Control Point (CTRL_PNT) + (Water Cool Hysteresis [P411]/2)
AND
current capacity is less than 10%
Related Parameters for Water Temperature Control:
Par.No
Description
Range
Default
407
Cool home set point – (cwoccstp): [°C]
5.0 ~ 18.0
12
408
Cool home offset – (cwunooff): [K]
0.0 ~ 10.0
0.0
409
Cool away offset – (cwecooff): [K]
0.0 ~ 10.0
0.0
411
Cool hysteresis – (cw_hyst)
0.5 ~ 2.0
0.5
521
User interface type – (ui-type)
0~3
0
•
Cooling control using room air temperature:
•
The operation of the heating mode is determined by the temperature sensor located inside the remote controller
•
The cooling operation will start when:
[1]
Room Air Temperature < Air Set point [P421] + Air Delta Set point [P428]
•
The heating operation will continue until:
[2]
Room Air Temperature > Air Set point [P421] + Air Delta Set point [P428]
OR
[3]
Room Air Temperature > Air Set point [P421]
AND
current capacity is less than 10%
Related Parameters for Room Air Temperature Control:
Par.No
Description
Range
Default
424
Cool home set point – (cloccstp): [°C]
20.0 ~ 38.0
26.0
425
Cool home offset – (clunooff): [K]
0.0 ~ 10.0
2.0
426
Cool away offset – (clecooff): [K]
0.0 ~ 10.0
4.0
428
Air delta setpoint – (deltastp)
0.5 ~ 2.0
1
521
User interface type – (ui-type)
0~3
0
OFF
[1]
Air Setpoint
(Room Air)
Room Air Temp.
(-) AirDeltaSetpoint
ON
Cooling Operation
[2]
[1]
[3]
(+) AirDeltaSetpoint
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...