Monobloc Outdoor Unit Service Manual
151
15.5.
High Pressure switch test
These service instructions describe the procedures and products to be used to check the correct operation of HP
switch in system, and verify and record the pressure target of high pressure switch.
Indeed, according to national regulations, check the protection devices on site in accordance with standards EN
378/ISO 5149: once a year for the high-pressure switches, every five years for external relief valves.
The procedure mentions here only the principle of a test without removing the pressure switch:
•
Connect a calibrated pressure gauge (with Schrader female port of ½ UNF)
•
Be ready to switch-off the main disconnect switch (on the unit or on the installation) of the power supply if the
pressure switch does not trigger (avoid over-pressure)
•
Complete an HP Switch Test as provided by the control system function:
Steps
Table
Par.
Designation
Description
Range Default Ex. Unit
Activate the
HP Switch
test
QCK_TEST
321 Quick Test enable Access to Quick test mode
0 to 1
0
1
-
323
Rating Mode
0 = Rating Off
1 = Rating Cool (set frequency with _RAT_FRQ
parameter)
2 = Rating Heat (set frequency with_RAT_FRQ
parameter)
3 = Ramp Cool (_RAT_FRQ corresponds to the
change rate Hz/min, ramp up if positive,
ramp down if negative).
4 = Ramp Heat (_RAT_FRQ corresponds to the
change rate Hz/min, ramp up if positive, ramp
down if negative).
Note: The Rating Mode is implemented for test
purpose (Lab tests, …). When the Rating Mode is
active, Water Control Point is ignored by the control.
The Pump is forced to run during the Rating Mode.
0 to 4
0
0
-
322
HP Switch Test
0 = HP Test Off
1 = HP Test Requested
2 = HP Test in Progress
3 = HP Test OK
4 = HP Test Failed due to timeout
5 = HP Test Failed due to Flow Switch Failure
6 = HP Test Failed due to Low Water Temperature
7 = HP Test Failed due to Inverter Failure
8 = HP Test failed due to high TL temperature
0 to 8
0
1
-
Wait until the HP switch test is finished: when [P322] = 3
321 Quick Test enable When the HP Switch test is finished, exit of quick
test mode
0 to 1
0
0
-
The Rating Mode is implemented for test purpose (Lab tests, …). When the Rating
Mode is active, Water Control Point is ignored by the control.
The Pump is forced to run during the Rating Mode.
If the test leads to replacing the pressure switch, it is necessary to recover the
refrigerant charge, these pressure switches are not installed on automatic valves
(Schrader type).
At least once a year, visually inspect the protection devices (valves, pressure
switches).
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...