Monobloc Outdoor Unit Service Manual
100
10.1.2.2. User Configuration Table
Access type: Read/Write
TABLE NAME: UI_CONF, PIC Table Type: 10H, instance 2
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
521
ui_type
0 to 3
0
-
User Interface Type
1
522
ui_accss
0 to 3
3
-
Parameter Access from UI
2
523
ui_tmt
0 to 240
60
s
Interface Comm. Timeout
3
524
ui_back
0 to 7
2
-
Backlight Timeout
4
525
ui_buzz
No / Yes
No
-
Buzzer on key press
526
timebrod
No / Yes
Yes
-
Interface Time Broadcast
5
527
ser_pass
0 to 9999
120
-
Service Password
528
usr_pass
0 to 9999
0
-
User Password
1.User interface type
0 = No user interface (WUI will not initiate communication)
1 = Remote control by contacts
2 = WUI remotely installed in the house (Remote)
3 = WUI locally installed on the unit (Local)
Note: If parameter 521 is set to "0", a WUI “Pocket” (used by a technician) can be temporarily connected to the unit for
parameters configuration.
Then, if this parameter 521 is set to "1", the WUI that is connected to the unit can be used for unit servicing and
monitoring, but the Operating Mode and Occupancy Mode selection will not be operative.
UI
Type
Unit
setting
Unit
Control
Unit
Monitoring
Scheduling Temp.
Type
Display
Remarks
0
No
Only
Time
and
DOW
WUI installed but not used.
WUI only responds to CCN
commands.
WUI used for unit configuration.
1
Water
Temp
Normal
Unit controlled by remote contacts
or unit is a Follower unit.
WUI used for unit configuration
and monitoring.
2
Air Temp
Normal
WUI installed in the house.
3
Water
Temp
Normal
WUI installed on the unit.
2. Parameter access for UI
0 = Access to parameters not allowed
1 = Access to User parameters only
2 = Access to User and Service parameters
3 = Access to User, Service and Factory parameters
3. UI communication timeout
If no communication message is received from the User
Interface for more than the timeout delay, the unit will be
stopped and the alarm will be activated. If this parameter
is set to 0, the communication timeout is ignored.
4. Backlight timeout
The backlight is switched off when no key is pressed
within a configured period of time:
0 = Backlight always off (disabled)
1 = 15 seconds
2 = 30 seconds
3 = 1 minute
4 = 2 minutes
5 = 5 minutes
6 = 30 minutes
7 = Always on (Backlight is always ON)
5. Time broadcaster
No = UI shall read the Date and Time in the Main
Controller
Yes = UI shall broadcast Date and Time over the Network
bus
IMPORTANT:
In order to make any changes introduced
in this menu effective, the power cycle is required.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...