Monobloc Outdoor Unit Service Manual
80
9.4.1.3.
Alarms 10 to 14 – Temperature sensors on inverter board
Electrical connection
Alarm 10
Discharge Temperature (TD) sensor failure
CN603 on MCC-1599
Alarm 11
Lower Air Temperature (TE) sensor failure
CN601 on MCC-1599
Alarm 12
Upper Air Exchanger Temperature (TL) sensor failure
CN604 on MCC-1599
Alarm 13
TO sensor failure
CN602 on MCC-1599
Alarm 14
Suction Temperature (TS) sensor failure
CN600 on MCC-1599
9.4.1.4.
Alarm 15 – Inverter heatsink temperature sensor failure
The sensor is located on the heatsink of the inverter box, it is not accessible.
Alarm 15
UI Indoor Temperature failure
If a failure occurs on the TH temperature sensor, then the inverter box must be changed:
9.4.1.5.
Alarm 16 – Inverter TE & TS sensors wrongly connected
Electrical connection
Alarm 16
Inverter TE & TS sensors wrongly connected
For TE: CN601 on MCC-1599
For TS: CN600 on MCC-1599
Change WUI (RC – remote controller)
Is sensor mounting correctly?
Are the resistance
characteristics of the
temperature sensor normal?
(check with resistance curve)
Replace defective sensor
Correct sensor mounting
Check inverter box and replace if defective
NO
YES
YES
NO
Is sensor correctly connected?
(refer to wiring diagram
Are the resistance
characteristics of the
temperature sensor normal?
(check with resistance curve)
Replace defective sensor
Correctly connect the sensor
Check inverter box and replace if defective
NO
YES
YES
NO
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...