Monobloc Outdoor Unit Service Manual
105
10.1.2.9. Header / Follower Configuration Table
Access type: Read/Write
TABLE NAME: MSL_CONF, PIC Table Type: 10H, instance 9
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
742
ms_sel
0 to 2
0
-
Header / Follower Selection
1
743
slv1_add
0 to 239
0
-
Follower #1 Address
2
744
slv2_add
0 to 239
0
-
Follower #2 Address
2
745
slv3_add
0 to 239
0
-
Follower #3 Address
2
751
casc_typ
0 to 2
1
-
Cascade Type
3
746
cap_strt
30 to 75
75
%
Capa. to Start Next Unit
752
ms_h_kp
0.001 to 10.000
0.900
-
M/S Heat Proport. Gain
753
ms_h_ti
10 to 120
30
s
M/S Heat Integral Time
754
ms_h_ts
10 to 120
30
s
M/S Heat Sampling Time
755
ms_c_kp
-10.000 to -0.001
-6.000
-
M/S Cool Proport. Gain
756
ms_c_ti
10 to 120
30
s
M/S Cool Integral Time
757
ms_c_ts
10 to 120
30
s
M/S Cool Sampling Time
758
ms_pmp
0 to 3
2
-
Header/Follower Pump Type
4
1. Header / Follower unit selection
0 = Disable (Unit operates in Standalone mode)
1 = Header
2 = Follower
2. Follower address
The address of the Follower unit. Please note that up to 3
Follower units can be configured to operate in the same
Header / Follower assembly.
3. Cascade type
This parameter is used to define the start/stop function
applicable to units operating in the same Header/Follower
assembly:
0 = Starting Header unit first, then Follower units are
started (beginning with the first Follower and ending with
the last Follower); Stopping process beginning with the
last Follower – the Header unit is stopped as the last one.
1 = Starting / Stopping units according to the wear factor
2 = All units, i.e. Header and Follower (s) are
started/stopped at the same time
4. Header / Follower pump type
This parameter is used to define pump control for units
operating in the Header/Follower assembly:
0 = No pump control
1 = Common Water Pump; a pump is installed outside the
unit on the water loop and it is controlled by the Header
2 = Individual Water Pump: Running according to the
Header/Follower overall status (Par. 229); each Header
or Follower unit has its own pump
3 = Individual Water Pump: Pump is stopped when the
unit is satisfied
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...