Monobloc Outdoor Unit Service Manual
43
[4] The system will stop producing DHW and the system will change back to heating mode when:
DHW_TT
≥
DHW_CTRLP [P406] -
∆
T DHW Stop [P722]
OR
The DHW maximum runtime [ P707] has elapsed
OR
The DHW exception timer [P708] has elapsed
[5] If there is DHW demand and the DHW Exception timer is OFF (timed out) then the system will continue to run
in heating mode. The system will only change to DHW mode if a second input pulse is received for the DHW
Priority function
Related Parameters for DHW Priority control:
Par.No
Description
Range
Default
209*
DHW exception timer – (DHW_EXCP): (min)
0 ~ 1440
-
406
DHW setpoint – (dhw_stp): (°C)
30.0 ~ 60.0
50.0
502~508** Customer switch (DI) configuration
0 ~ 8
0
707***
DHW max. runtime – (dhw_max): (min)
-1 (or 30)~720
60
708
DHW exception time – (dhw_excp): (hr)
1 ~ 24
2
711
DHW schedule days – (dhw_dow): (-)
0000 0000
1111 1111
1111 1110
712
DHW start time – (dhw_strt): (hr:min)
00:00 ~ 23:59
21:00
713
DHW stop time – (dhw_stop): (hr:min)
00:00 ~ 23:59
06:00
721
DHW tank
∆
T (start) – (dhw_dt): (K)
2.0 ~ 10.0
5.0
722
DHW tank
∆
T (stop) – (dhw_dts): (K)
0.0 ~ 5.0
0.0
* [P209] shows the status of the DHW exception timer (real time)
** Parameter required depends on DI selected. For example if DI#05 is used for the DHW Priority function
then [P502] needs to be set to 6
*** If [P707] = -1 then the DHW maximum runtime is ignored
8.2.9.
Anti-Legionella Control
The water inside the domestic water tank must be constantly controlled in order to minimize the risk of any
contamination, including legionella bacteria. Legionella belongs to a group of bacteria that is likely to grow in the water
system if proper measures are not taken.
The system can be scheduled to heat up water in the domestic hot water tank in order to eliminate the possibility of
legionella growth or kill the existing bacteria.
To reduce the risk of Legionella bacteria growth water should be stored at 50°C or higher.
Anti-Legionella ON:
The anti-legionella control will switch ON
The anti-bacteria control cycle can be enabled by two different methods:
i)
Manual Operation
Manual operation of the anti-bacteria is achieved by configuring one of the custom DI’s to “anti-legionella cycle
request switch”.
Set the relevant software parameter ([P502] ~ [P505]), depending on the DI selected for the anti-legionella cycle
(if DI_02 was used then P503 =)
When the status of the selected DI changes from OPEN to CLOSE. The DHW production control will be enabled
with the required anti-legionella set-point [P405].
Anti-Legionella OFF:
The anti-legionella control will switch OFF when:
•
DHW_TT > leg_stp [P405] -
∆
T DHW Stop [P722]
OR
•
6 hour internal timer has elapsed
ii)
Automatic Operation
The anti-legionella control cycle can also be operated automatically using the anti-legionella schedule function:
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...