Monobloc Outdoor Unit Service Manual
107
10.1.3.
Display tables
10.1.3.1. General Unit Table
Access type: Read-only (force is possible)
TABLE NAME: GENUNIT, PIC Table Type: 11H, instance 1
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
1
OAT
-40.0 to 115.6
-
°C
Outdoor Air Temperature
2
IAT
-40.0 to 115.6
-
°C
Indoor Air Temperature
1
3
EWT
-40.0 to 115.6
-
°C
Entering Water Temp
4
LWT
-40.0 to 115.6
-
°C
Leaving Water Temp
5
TR
-40.0 to 115.6
-
°C
Refrigerant Temperature
6
SPARE_T
-40.0 to 115.6
-
°C
Spare Temperature
2
7
roomtemp
-40.0 to 115.6
-
°C
Room Temperature
3
8
sst
xxx.x
-
°C
Saturated Suction Temp
9
ts
xxx.x
-
°C
Suction Temperature
10
td
xxx.x
-
°C
Discharge Temperature
11
te
xxx.x
-
°C
Lower Air Exchanger Temp
12
tl
xxx.x
-
°C
Upper Air Exchanger Temp
13
to
xxx.x
-
°C
Inv. Outdoor Air Temp
4
39
to2
xxx.x
-
°C
Corrected Inverter TO
5
14
th
xxx.x
-
°C
Heatsink Temperature
15
Sh
xxx.x
-
^C
Superheat Temperature
16
sh_targ
xxx.x
-
^C
Superheat Target Temp
17
dc_volt
xxx
-
V
Inverter DC High Voltage
18
hv_stat
Normal/Alarm
-
-
HV Bus Comm. Status
6
19
inv_mod
0/1/2/7/21/22
-
-
Inverter Current Mode
7
20
freq_min
xxx.x
-
Hz
Actual Min Compr. Freq
21
freq_max
xxx.x
-
Hz
Actual Max Compr. Freq
22
FREQ_REQ
0.0 to 120.0
-
Hz
Requested Compr. Freq
8
23
freq_cur
xxx.x
-
Hz
Actual Compressor Freq
24
pmv_pos
xxxx
-
-
PMV Position
27
upr_fan
Xxxx
-
rpm
Upper Fan Speed
28
lwr_fan
Xxxx
-
rpm
Lower Fan Speed
29
EXCH_HTR
Off / On
-
-
Exchanger Elec. Heater
30
BOILER
Off / On
-
-
Boiler
31
EHS
0 to 3
-
-
Electrical Heat Stages
35
SPARE_P
xxx.x
-
PSI
Spare Pressure
9
1. Indoor Air Temperature
This value corresponds to "Room Temperature" [P007] + "IAT
Sensor Bias" [P512].
2.
Spare temperature:
Not applicable
3. Room temperature
This value is received from the WUI.
4. Inverter Outdoor Air Temperature
This parameter provides OAT measurement used to determine the
control of PMV. The sensor is located on the coil.
5. Corrected Inverter TO
Sometimes due to coil temperature in Cooling, the Inverter OAT
measurement [P013] may not be 100% accurate; therefore, the
control computes and provides the corrected Inverter OAT [P039].
6. HV communication status
0 = Normal
1 = Alarm
7. Inverter mode
0 = Off
1 = Heating
2 = Cooling
7 = Defrost
21 = Cool demand satisfied
22 = Heat demand satisfied
8. Compressor frequency (read-only)
This variable cannot be forced manually.
9. Spare pressure: Not applicable
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...