Monobloc Outdoor Unit Service Manual
72
To reset alarms
1.
In the alarm menu, press and hold the
Mode
key and the
Schedule
key simultaneously for 2 seconds.
2.
The reset alarm menu will be displayed.
3.
Press the
Down
key or the
Up
key to set the alarms reset to
“YES”.
Alarm reset: NO
Alarm reset: YES
4.
To confirm the alarms reset, press and hold the Mode key and
the Schedule key simultaneoulsy for 2 seconds.
To exit the alarm screen
1.
Press and hold the
Occupancy
key until the home screen is
displayed.
RC Errors
Some components failure may cause the RC to malfunction. In such cases, the error will be displayed on the screen.
Example E1
ID
Description
E1
Communication failure
E2
Wrong configuration (Unit not configured to use RC)
E3
Profile table wrong size
E4
Parameter not found but mandatory
E5
Room Sensor failure
Access the parameter menu on the remote controller
Use the Up & Down arrows to select the following alarm parameters:
•
Inverter Alarm [P344]
•
NHC Current alarm #1 [P346] to NHC current alarm #5 [P349]
•
NHC Past alarm #1 [P350] to NHC past alarm #5 [P354]
9.3.3.
How to cancel a check code
If the defect is limited by the check code displayed on the remote controller, please repair the defect based on the
tables in
9.3.5
.
Depending on check code, reset is completed by either;
•
Automatic, on completion of corrective action, or
•
By power cycle (Off/On)
See following tables for alarm reset procedure by check code, including investigation and corrective actions.
9.3.4.
How to determine the defect error by inverter board LED display
LED display on inverter board is to use only if there is a problem on alarm readiness by
remote controller or Proprietary Protocol. Otherwise give priority to alarm read from
parameters: [P344, Current alarm [P346] to [P349], and Past alarm [P350] to [P354],
refer to table in 9.3.5
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...