Monobloc Outdoor Unit Service Manual
150
4. Clean the filter with water
5. Replace the screen filter and screw back in
15.4.3.
Pump
The following is a check list for fixed speed pump procedures:
Action
Reference
Note
Follow Installation and Operation manual for
installation and start up
IOM
Ensure that all lines supplying the pump have
been flushed before the pump is installed
Clean liquid prevent pump wearing
Check that all filtering / straining devices are
clear of debris and have positive inlet pressure
Low inlet pressure may cause
pump cavitation
Measure electric insulation
23 ohms between phases
Check for proper motor rotation
Wrong rotation may cause
mechanical seal damages and low
water flow.
Measure motor currents value at duty point and
verify proper motor protection set-up
Motor data label
The motor currents may be saved
used for predictive maintenance
Check for proper voltage (under load, as close to
the motor as possible)
Check for leaks and ensure all fittings are
properly tightened
Bump start the pump and listen for any unusual
sounds measure vibration in correspondence of
motor shield
The motor vibration may be saved
used for predictive maintenance
Check:
- water flow rate according the selection - flow
switch status and pressure
-measure pressure at zero flow
The motor vibration may be saved
used for predictive maintenance
No check is to be done on variable speed pump, if VS pump doesn’t operate, it is
necessary to replace the VS pump.
Water filter
Unscrew filter and
remove the screen
filter
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...