Monobloc Outdoor Unit Service Manual
46
Control overview:
(1) With the system powered, but not running, the Monobloc unit starts in heating mode when the room
temperature is less than the temperature set in [P427]. At this time:
•
The main water pump is ON
•
The electrical booster heaters are OFF
•
The additional pump is OFF
(2) When the room air temperature increases to the temperature set in [P427] plus 2°C then the Monobloc unit
switches OFF. The system will not restart in the Home Anti-Freeze Protection until the room temperature
drops below the control threshold temperature set in [P427]
Please note that the home anti-freeze protection is active even when the unit is in the OFF mode (not in Cooling /
Heating / DHW).
Related parameters for the home anti-freeze protection control:
Par.No
Description
Range
Default
427
Home anti-freeze setpoint – (freexstp): (°C)
6.0 ~ 12.0
6.0
Never switch off the unit, otherwise home anti-freeze protection cannot be guaranteed. For this reason the
main unit and / or customer circuit disconnect switch must always be left closed.
8.2.13.
Auto / climatic curve operation
The auto or climatic curve control automatically sets the water temperature set-point depending on the outside air
temperature (OAT).
Auto curve control is available for both heating and cooling functions. There are two types of auto curve available:
•
Custom
•
Predefined
i) Cooling mode:
Auto curve control, for cooling mode operation, can be enabled by setting the Cool Clim Curve Select parameter
[P586] as shown below:
Par.No
Setting
Function
586
-1
No curve (fixed water temperature)
0
Custom climatic curve
1
Cooling climatic curve 1
2
Cooling climatic curve 2
•
Custom climatic curve:
If the cooling climatic curve is configured to "0", the water set-point will be calculated according to the custom cooling
climatic curve.
Parameters
Description
Default
Minimum
Maximum
cl_min_a
587
Custom Minimum OAT
20.0°C
0°C
30°C
cl_max_a
588
Custom Maximum OAT
35.0°C
24°C
46°C
cl_min_w
589
Custom Minimum Water Temp
10.0°C
5°C
18°C
cl_max_w
590
Custom Maximum Water Temp
18.0°C
5°C
18°C
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...