Monobloc Outdoor Unit Service Manual
98
10.1.1.2. Compressor Factory Table
Access type: Read/Write
TABLE NAME: CMP_FACT, PIC Table Type: 13H , instance 2
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
821
heat_kp
0.001 to 10.000
0.900
-
Heat Ctrl Proport. Gain
822
heat_ti
10 to 120
30
s
Heat Ctrl Integral Time
823
heat_ts
10 to 120
30
s
Heat Ctrl Sampling Time
824
cool_kp
-10.000 to -0.001
-0.900
-
Cool Ctrl Proport. Gain
825
cool_ti
10 to 120
30
s
Cool Ctrl Integral Time
826
cool_ts
10 to 120
30
s
Cool Ctrl Sampling Time
10.1.1.3. Update Hours and Starts Number Table
Access type: Read/Write or Read-only (see a note below the table)
TABLE NAME: UPDTHOUR, PIC Table Type: 13H, instance 3
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
841
comp1_st
-
-
-
Compressor Starts Nb
842
comp1_hr
-
-
h
Compressor Run Hours
843
pmp_st
-
-
-
Water Pump Starts Nb
844
pmp_hr
-
-
h
Water Pump Run Hours
Once the compressor has been started, the UPDTHOUR table is normally read-only. However, it is possible to modify
the table in the case of NHC board replacement before the compressor has been started. Afterwards, parameters
given in the table above cannot be changed.
10.1.2.
Configuration tables
10.1.2.1. General Configuration Table
Access type: Read/Write
TABLE NAME: GEN_CONF, PIC Table Type: 10H, instance 1
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
501
sfsw_typ
1 to 3
1
-
Safety Switch Type
1
502
cust_di5
0 to 15
1
-
Customized DI #5 Config
2
503
cust_di6
0 to 15
0
-
Customized DI #6 Config
2
504
cust_di7
0 to 15
0
-
Customized DI #7 Config
2
505
cust_di8
0 to 15
0
-
Customized DI #8 Config
2
506
cust_do8
0 to 12
1
-
Customized DO #8 Config
3
507
cust_do9
0 to 12
2
-
Customized DO #9 Config
3
508
tr_type
0 to 2
0
-
Refrigerant Temp Type
4
509
ewt_type
0 to 2
1
-
EWT Sensor Type
5
510
iat_type
0 to 3
0
-
IAT Sensor Type
6
511
oat_type
0 to 3
0
-
OAT Sensor Type
7
520
sparetyp
0 to 5
0
-
Spare Sensor Type
8
512
iat_bias
-5.0 to 5.0
0.0
^C
IAT Sensor Bias
513
oat_bias
-5.0 to 5.0
0.0
^C
OAT Sensor Bias
514
oat_min
-20.0 to 10.0
-20.0
°C
Minimum OAT for Heating
9
515
oat_max
5.0 to 30.0
30.0
°C
Maximum OAT for Heating
10
516
oat_minc
-10.0 to 40.0
-10.0 or 0.0
°C
Minimum OAT for Cooling
11
517
freez_dt
0.0 to 6.0
0.0
^C
Anti-Freeze Delta Setpoint
12
518
nghtstrt
00:00 to 23:59
00:00
-
Night Mode Start Time
13
519
nghtstop
00:00 to 23:59
00:00
-
Night Mode Stop Time
13
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...