Monobloc Outdoor Unit Service Manual
106
10.1.2.10. JBus configuration table
Access type: Read/Write
TABLE NAME: JBUSCONF, PIC Table Type: 10H, instance 10
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
761
jbus_ena
0 to 2
2
-
JBus Control Enable
1
762
jbus_add
1 to 255
11
-
JBus Follower Address
646
jbus_bdr
0 to 2
2
-
JBus Baud Rate
2
764
jbus_frm
0 to 5
0
-
JBus Frame Type
3
766
jbus_tmt
0 to 600
600
s
JBus Comm. Timeout
4
767
mbusoff1
0 to 61440
16384
-
Modbus Display Offset
5
768
mbusoff2
0 to 61440
32768
-
Modbus Setpoint Offset
5
769
mbusoff3
0 to 61440
28672
-
Modbus Config. Offset
5
770
mbusoff4
0 to 61440
36864
-
Modbus Service Offset
5
1. JBus enable
0 = JBus/Modbus communication disabled
1 = JBus communication enabled
2 = Modbus communication enabled
JBus and Modbus protocols are similar except for the
addressing:
JBus: To access register n, use "n" address.
Modbus: To access register n, use "n-1" address.
2. JBus baud rate
0 = 9600 bauds
1 = 19200 bauds
2 = 38400 bauds
3. JBus baud frame
0 = No parity, 1 stop bit
1 = Odd parity, 1 stop bit
2 = Even parity, 1 stop bit
3 = No parity, 2 stop bits
4 = Odd parity, 2 stop bits
5 = Even parity, 2 stop bits
4. JBus timeout
If no JBus request is received for more than the timeout
delay, the unit will be stopped and an alarm will be
activated. If this parameter is configured to "0", the
timeout is ignored
5. Modbus offset
Those parameters are considered only in Modbus
configuration ([P761]=2).
Parameter
Type
Modbus
offset
Section
length
Parameter offset
(if ModbusOffset > 0)
Display
0x4000
0x3000
0
Setpoint
0x8000
0x1000
400
Configuration
0x7000
0x1000
500
Service
0x9000
0x1000
800
ModbusRegister = Param ModbusOffset –
ParamOffset – 1
Note: If configured Modbus Offset is null, Parameter
Offset is ignored.
For example,
“Cool Home Water Setpoint”
[P408] which
corresponds to JBus register 0x0198, will corresponds to
Modbus register 0x8007.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...