Monobloc Outdoor Unit Service Manual
60
8.3.3. Water Pump override [P081]
The following table includes water pump overrides which are used to ensure the proper functioning of the
unit.
#
Override
Conditions
Action
-1
Pump Disabled
No pump is configured
Do nothing
1
Compressor still
running
Compressor is requested to stop
but is still running
Keep running the pump
2
Flow Switch Failure
No water flow detected
Stop the pump; do not allow the
compressor to run.
3
Stopping Delay
Pump is requested to stop
Continue to run the pump for 30
seconds, and then stop it.
4
Anti-sticking
Anti-sticking function is enabled
and pump has not run for 24 hours.
Run the pump for 30 seconds
5
Low OAT
Pump is not running <AND>
OAT < MinimumC
AntiFreezeDeltaSetpoint [P517] +
4K (AntiFreezeDeltaSetpoint is 0 K
by default)
Run the pump at maximum
configured speed for 1 minute
every 15 minutes
6
Very Low OAT
Pump is not running <AND> OAT
< MinimumC
AntiFreezeDeltaSetpoint [P517] +
4K <AND> EWT or LWT <
MinimumC
AntiFreezeDeltaSetpoint [P517] +
1K (AntiFreezeDeltaSetpoint is 0 K
by default)
Run the pump continuously at
maximum configured speed
7
Defrost active
Defrost is active
Run the pump at maximum speed
8
Boiler active
Boiler active and Compressor is
not running
Stop the pump
9
DHW Active
a) DHW Active <AND> dhw_type =
1 or 2 (Par.701) <AND>
Compressor is running b) DHW
Active <AND> dhw_type = 1 or 2
(Par.701) <AND> Compressor is
stopped c) DHW Active <AND>
dhw_type = 3 (Par.701)
a) Run the Pump at configured
speed for DHW (Par.710)
b) Run the Pump at minimum
speed (Par.567) c) Stop the pump
10
Master/Slave
Master/Slave is active <AND> unit
is Slave <AND> “PMP” parameter
is forced by the Master.
Pump is controlled by the master
11
Water Sampling
Satisfied state and Water Sampling
logic is selected (Par.565=2)
Run the pump for 2 minutes every
Par.564 minutes.
12
Purge
Purge Mode active
Run the pump continuously at
maximum speed regardless of the
Water Flow status
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...