10.1.2.5. Climatic Curves Table
Access type: Read/Write
TABLE NAME: CLIMCURV, PIC Table Type: 10H, instance 5
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
581
ht_curv
-1 to 12
-1
-
Heat Clim Curve Select
1
582
ht_min_a
-30.0 to 10.0
-7.0
°C
Heat Minimum OAT
583
ht_max_a
10.0 to 30.0
20.0
°C
Heat Maximum OAT
584
ht_min_w
20.0 to 40.0
20.0
°C
Heat Min Water Setpoint
585
ht_max_w
30.0 to 60.0
38.0
°C
Heat Max Water Setpoint
586
cl_curv
-1 to 2
-1
-
Cool Clim Curve Select
2
587
cl_min_a
0.0 to 30.0
20.0
°C
Cool Minimum OAT
588
cl_max_a
24.0 to 46.0
35.0
°C
Cool Maximum OAT
589
cl_min_w
5.0 to 20.0
10.0
°C
Cool Min Water Setpoint
590
cl_max_w
5.0 to 20.0
18.0
°C
Cool Max Water Setpoint
1. Heating climatic curve select
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve using the following
parameters (Par.582 to Par.585)
1 = Heating Climatic Curve #1
2 = Heating Climatic Curve #2
3 = Heating Climatic Curve #3
4 = Heating Climatic Curve #4
…
12 = Heating Climatic Curve #12
2. Cooling climatic curve select
-1 = No Curve / Fixed Water Setpoint
0 = Custom Climatic Curve using the following
parameters (Par.587 to Par.590)
1 = Cooling Climatic Curve #1
2 = Cooling Climatic Curve #2
The option to control the water temperature based on the
climatic curve applies only to units that have system
control based on water temperature control, not air
temperature control.
With a custom climatic curve, be careful to configure the Maximum OAT greater than the Minimum OAT.
Otherwise the setpoint will be forced to the Maximum Water Temp.
Heat Maximum Water Setpoint can be offsetted by User Configurable [P412] (the top possible value of the
heating climatic curve).
Cool Minimum Water Setpoint can be offsetted by User Configurable [P413] (the lowest possible value of the
cooling climatic curve).
In Sleep Mode, the control point based on the climatic curve will be offsetted either by [P402] (Heat Sleep
Offset) or [P408] (Cool Sleep Offset).
In Away Mode, the control point based on the climatic curve will be offsetted either by [P403] (Heat Away
Offset) or [P409] (Cool Away Offset).
10.1.2.6. Drying Mode Table
Access type: Read/Write
TABLE NAME: DRYING, PIC Table Type: 10H, instance 6
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
595
dry_stp
20.0 to 40.0
20.0
°C
Drying Starting Setpoint
596
drystep1
0 to 99
3
-
Drying Warm-up days
597
drystep2
0 to 99
4
-
Drying Ramp-up days
598
drystep3
0 to 99
4
-
Drying Hold-up days
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...