Monobloc Outdoor Unit Service Manual
116
10.1.4.3. Alarm Table
Access type: Read-only (force is possible)
TABLE NAME: ALARM, PIC Table Type: 12H, instance 3
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
340
ALMRESET
No / Yes
No
-
Alarm Reset
341
ALM
Normal / Alarm
Normal
-
Alarm Status
1
342
ALERT
No / Yes
No
-
Alert Status
1
343
SHUTDOWN
No / Yes
No
-
Shutdown Status
1
344
inv_err
0 to 255
-
-
Inverter Error (Code)
2
345
inv_erra
Normal/“Xnn”
-
-
Inverter Error (Alpha)
2
350
alm_01
xx
0
-
Current Alarm #1
351
alm_02
xx
0
-
Current Alarm #2
352
alm_03
xx
0
-
Current Alarm #3
353
alm_04
xx
0
-
Current Alarm #4
354
alm_05
xx
0
-
Current Alarm #5
360
alm_01p
xx
0
-
Past Alarm #1
361
alm_02p
xx
0
-
Past Alarm #2
362
alm_03p
xx
0
-
Past Alarm #3
363
alm_04p
xx
0
-
Past Alarm #4
364
alm_05p
xx
0
-
Past Alarm #5
1. ALM / ALERT / SHUTDOWN (read-only)
These points cannot be forced; these are read-only
parameters.
2. Inverter Error Code
0 = “Normal”: no error
100 = “F04”: TD sensor open or short
102 = “F06”: TE sensor open or short
103 = “F07”: TL sensor open or short
104 = “F08”: TO sensor open or short
108 = “F12”: TS sensor open or short
109 = “F13”: TH sensor open or short
111 = “F15”: TE & TS sensors incorrectly connected
119 = “F23”: PS sensor open or pressure too high
127 = “F31”: Not able to communicate with EEPROM or
EEPROM number out of range
129 = “H01”: Compressor breakdown
130 = “H02”: Compressor lock
131 = “H03”: Outdoor unit current detection circuit error
132 = “H04”: Compressor Case Temperature too high
(thermal Switch open)
134 = “H06”: Suction Pressure too low
221 = “L29”: Communication failure between MCUs
227 = “P03”: TD too high
228 = “P04”: High Pressure Switch activated
229 = “P05”: Missing phase in power cable
231 = “P07”: Heatsink Temperature too high
243 = “P19”: 4-way valve not in the right position
244 = “P20”: High pressure protective operation
246 = “P22”: Outdoor fan system error
250 = “P26”: Outdoor unit inverter short circuit protection
253 = “P29”: Outdoor unit motor position detection error
Note: This Inverter Error Code is coming from HV bus
Command BAH Byte 2.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...