Monobloc Outdoor Unit Service Manual
48
Related parameters for cooling climatic curve control (predefined and custom):
Par.No
Description
Range
Default
408
Cool sleep offset – (cwunooff): (K)
0.0 ~ 10.0
0.0
409
Cool away offset – (cwecooff): (K)
0.0 ~ 10.0
0.0
413
Cool curve min. set-point offset – (ccurvoff): (K)
-5.0 ~ 5.0
0.0
586
Cool clim curve select – (cl_curv)
-1 ~ 2
-1
587
Cool minimum OAT – (cl_min_a): (°C)
0.0 ~ 30.0
20.0
588
Cool maximum OAT – (cl_min_a): (°C)
24.0 ~ 46.0
35.0
589
Cool min. water set-point – (cl_min_w): (°C)
5.0 ~ 20.0
10.0
590
Cool max. water set-point – (cl_min_w): (°C)
5.0 ~ 20.0
18.0
ii)
Heating mode:
Auto curve control, for heating mode operation, can be enabled by setting the Heat Clim Curve Select parameter
[P581] as shown below:
Par.No
Setting
Function
581
-1
No curve (fixed water temperature)
0
Custom climatic curve
1
Heating climatic curve 1
12
Heating climatic curve 12
•
Custom climatic curve:
If the heating climatic curve [ht_curv] is configured to "0", the water set-point will be calculated according to the
custom heating climatic curve. This custom heating climatic curve can be defined using the following parameters in
the CLIMCURV table:
Parameters
Description
Default
Minimum Maximum
ht_min_a
582
Custom Minimum OAT
-7.0°C
-30°C
10°C
ht_max_a
583
Custom Maximum OAT
20.0°C
10°C
30°C
ht_min_w
584
Custom Minimum Water Temp
20.0°C
20°C
40°C
ht_max_w
585
Custom Maximum Water Temp
38.0°C
30°C
60°C
•
If OAT is invalid, the Water Setpoint is equal to the Custom Max. Water Temp.
•
If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the Custom Min. Water
Temp.
If Min. OAT is greater or equal to Max. OAT threshold, the Water Setpoint is equal to the custom Max. Water Temp.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...