Monobloc Outdoor Unit Service Manual
75
9.3.5.
How to diagnose by error code
Check Code
Determination and action
A
lar
m
[
P
3
44]
C
ur
ren
t A
lar
m
[P
346
] t
o [
P
3
49]
P
a
s
t A
la
rm
[P
350
] t
o [
P
3
54]
Operational Cause
Unit Status
Automatic
Reset
-
1
EWT sensor failure
Continue
X
Automatic reset when the sensor returns within the correct range.
1. Check EWT sensor (EWT)
2. Check NHC board
-
2
LWT sensor failure
Stop
X
Automatic reset when the sensor returns within the correct range.
1. Check LWT sensor (LWT)
2. Check NHC board
-
3
Refrigerant Temperature
(TR) sensor failure
Compressor
stop
X
Automatic reset when the sensor returns within the correct range.
1. Check TR sensor (TR)
2. Check NHC board
-
4
OAT sensor failure
Continue
X
Automatic reset when the sensor returns within the correct range.
1. Check additional OAT sensor (OAT)
2. Check NHC board
-
5
DHW_TT sensor failure
DHW failed
X
Automatic reset when the sensor returns within the correct range.
1. Check DHW sensor (DHW)
2. Check NHC board
-
6
CHWSTEMP sensor failure
X
Automatic reset when the sensor returns within the correct range.
1. Check CHWSTEMP sensor (CHWSTEMP)
2. Check NHC board
-
7
IAT sensor failure
Continue
X
Automatic reset when the sensor returns within the correct range.
1. Check IAT sensor (IAT)
2. Check NHC board
-
8
RC indoor temperature
failure
Continue
X
Automatic reset when the sensor returns within the correct range.
1. Check RC indoor temperature sensor
2. Check NHC board
-
9
Spare sensor failure
Continue
X
Automatic reset when the sensor returns within the correct range.
1. Check spare sensor
2. Check NHC board
100
10
Inverter discharge
temperature (TD) sensor
failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 4 times.
1. Check discharge temperature sensor (TD)
102
11
Inverter air exchanger
temperature (TE) sensor
failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 4 times.
1. Check temperature sensor (TE)
103
12
Inverter liquid temperature
(TL) sensor failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 4 times.
1. Check temperature sensor (TL)
104
13
Inverter TO sensor failure
Continue
O
Alarm reset by resetting the power supply to the Monobloc unit.
Unit operation continues in backup mode. TO sensor value fixed to 30°C in
cooling, 10°C in heating. Backup mode is cancelled when any other value is
detected by TO sensor.
1. Check outside temperature sensor (TO)
108
14
Inverter Suction Temperature
(TS)
Sensor failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 4 times.
1. Check suction temperature sensor (TS)
109
15
Inverter heatsink
temperature failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 8 times.
1. Check correct fan operation
111
16
Inverter TE & TS sensors
wrongly connected
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation 4 times.
1. Check temperature sensor (TE, TS)
119
17
Inverter suction pressure
(PS) sensor failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 2 times for disconnection
detection and 4 times for high pressure.
1. Check suction pressure sensor (LP)
-
20
Loss of communication with
RC
Continue
X
Alarm reset when a new message is received from the RC
1. Check RC connections (RC & Monobloc)
-
21
Loss of communication with
inverter
Compressor
stop
X
Alarm reset when a new message is received from the inverter.
1. Check connections between inverter PCB & NHC board
221
22
Loss of communication
between inverter PCB’s
Compressor
stop
O
Alarm caused by delay in communication. Alarm reset by resetting the power
supply to the Monobloc unit.
-
23
Loss of communication with
Follower units
Header
continues
X
If the Header unit cannot communicate with Follower units for 10 minutes
Automatic reset when communication between Follower units is restored.
-
24
Loss of communication with
Header unit
Stop
X
If the Follower units cannot communicate with Header unit for 10 minutes
Automatic reset when communication with the Header unit is restored.
-
31
Safety input
Unit stop OR
heat stop OR
cool stop
X
Automatic reset when the safety input is closed.
-
32
Flow switch failure
Compressor
stop
O
Alarm reset by resetting the power supply to the Monobloc unit. Error
becomes definite after retrying operation for 5 times.
1. Check flow switch operation / connections
2. Check / clean water filter
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...