Monobloc Outdoor Unit Service Manual
40
8.2.6.
Simultaneous Cooling and Domestic Hot Water Operation:
It is possible to operate the ESTIA Monobloc system with both space heating and domestic hot water modes selected
on the remote controller / software parameters. The operating mode is selected as detailed below and depends on the
outdoor air temperature (OAT).
•
Cooling and DHW simultaneous control:
[1] When the system is operating in space cooling (SC) mode and the
Space Cooling Minimum Runtime
[P704]
has elapsed
AND
the temperature of the water, inside the DHW cylinder, is less than
CTRL_PNT
[P406] -
∆
T
DHW Start
[P721] then the system will STOP space Cooling and will change over to DHW production mode. The
operating sequence for the system at this point is:
•
The compressor continues to run
•
The water pump continues to run
•
The 3 way valve changes position to allow DHW production
•
The DHW Set point [P406] is displayed on the remote controller
•
The electric heater, for the DHW cylinder is allowed to start
[2] The system will operate in DHW production mode until
DHW_TT > CTRL_PNT [P406] – 1K [P722]
OR
until the
DHW Maximum Runtime
[P707] At this point the DHW temperature, inside the DHW cylinder, will be satisfied
and the system will change back to space heating operation
NOTE:
The DHW, inside the DHW cylinder, will be produced using only the electric heater installed in the cylinder under the
following conditions:
•
OAT < Minimum OAT for cooling
[P516]
•
OAT > Maximum OAT for heating
[P515]
•
If there is a fault on the ESTIA Monobloc outdoor unit
Related Parameters for Simultaneous Cooling and DHW Control:
In addition to the parameters detailed for DHW only and Cooling only operation the following parameters are related to
the simultaneous Cooling and DHW system control
Par.No
Description
Range
Default
704
SHC minimum runtime – (shc_min): [min]
0 ~ 720
20
707
DHW maximum runtime – (dhw_max): [min]
-1(or 30)~720*
60
*If [P707] is configured to -1 then the DHW maximum runtime is ignored
Space Cooling Mode
OFF
∆T Start [P721]
Space Cooling Setpoint
ON
DHW Operation
OFF
ON
∆T Stop [P722]
[1]
[2]
[1]
[2]
DHW Setpoint [P406]
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...