Monobloc Outdoor Unit Service Manual
36
8.2.3. Heating Operation
•
The operation of the heating mode is determined by the water temperature measured by the LWT sensor
•
The heating operation will start when:
[1]
Control Temperature (CTRL_TMP)< Control Point (CTRL_PNT) – Water Heat Hysteresis [P410]
•
The heating operation will continue until:
[2]
Control Temperature (CTRL_TMP)>Control Point (CTRL_PNT) + (Water Heat Hysteresis [P410]
OR
[3]
Control Temperature (CTRL_TMP) > Control Point (CTRL_PNT) + (Water Heat
Hysteresis [P410]/2)
AND
current capacity is less than 10%
Related Parameters for Water Temperature Control:
Par.No
Description
Range
Default
401
Heat home set point – (hwoccstp): [°C]
20.0 ~ 60.0
45
402
Heat home offset – (hwunooff): [K]
-10.0 ~ 0.0
0.0
403
Heat away offset – (hwecooff): [K]
-10.0 ~ 0.0
-5.0
410
Heat hysteresis – (hw_hyst)
0.5 ~ 2.0
2
521
User interface type – (ui-type)
0~3
0
•
Heating control using room air temperature:
The heating operation is controlled by the system
Room Air Temperature
and the system
Heat Home Setpoint
(htoccstp) [P421]. The Control Temperature is measured by the leaving water temperature sensor [P004].
To prevent the system short cycling in heating, mode using air temperature control, the
Air Delta Setpoint
(deltastp)
[P428] parameter must be set.
The
Heat Home Setpoint
(htoccstp) [P421] has to be set for each of the occupancy modes. This is achieved by
applying an offset to the
Heat Home Setpoint
(htoccstp) set for the “HOME” mode. The offsets are applied by setting
parameters [P422 – Heat Sleep Offset] and [P423 – Heat Away Offset].
Room Air Temperature = measured by thermistor in the remote controller
Heat Home Setpoint (htoccstp)= room air set point temperature
Air Delta Setpoint (deltastp) = [P428]
•
The operation of the heating mode is determined by the temperature sensor located inside the remote
controller
•
The heating operation will start when:
[1]
Room Air Temperature < Air Set point [P421] – Air Delta Set point [P428]
ON
[1]
Room Air Temp.
(+) AirDeltaSetpoint
Air Setpoint
(Room Air)
(-) AirDeltaSetpoint
OFF
Heating Operation
[1]
[3]
[2]
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...