Monobloc Outdoor Unit Service Manual
104
10.1.2.8. Domestic Hot Water Configuration Table
Access type: Read/Write
TABLE NAME: DHW_CONF, PIC Table Type: 10H, instance 8
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
701
dhw_type
0 to 3
0
-
Domestic Hot Water Type
1
702
dhw_vlvr
0 to 240
30
s
DHW 3-way Valve run time
704
shc_min
0 to 720
20
min
SHC Minimum Runtime
707
dhw_max
-1 (or 30) to 720
60
min
DHW Maximum Runtime
2
708
dhw_excp
1 to 24
2
hour
DHW Exception Time
710
dhw_vsp
19 to 100
100
%
Pump Speed in DHW
711
dhw_dow
0000 0000 to 1111
1110
1111 1110
-
DHW Schedule Days
3
712
dhw_strt
00:00 to 23:59
21:00
hh:mm
DHW Starting Time
713
dhw_stop
00:00 to 23:59
06:00
hh:mm
DHW Stopping Time
714
leg_dow
0000 0000 to 1111
1111
0000 0000
-
AntiLegionella Strt DOW
4
715
leg_time
00:00 to 23:59
02:00
hh:mm
AntiLegionella Strt Time
716
sum_oat
15.0 to 30.0
20.0
°C
Summer Mode OAT Thrshold
717
sum_on
0 to 12
5
h
Summer Mode On Delay
5
718
sum_off
0 to 12
5
h
Summer Mode Off Delay
5
719
dhw_sens
0 to 3
0
-
DHW Tank Sensor Type
6
720
dhw_bias
-5.0 to 5.0
0.0
^C
DHW Tank Sensor Bias
721
dhw_dt
2.0 to 10.0
5.0
^C
DHW Tank Delta T (start)
7
1. Domestic hot water type
0 = No DHW management
1 = Diverting Valve NO 2-points
(valve energized in DHW position)
2 = Diverting Valve NC 2-points
(valve de-energized in DHW position)
3 = Dedicated DHW Circulator or Pump
2. Maximum runtime
If this parameter is configured to -1, DHW Runtime is ignored.
3. DHW days schedule
Domestic hot water priority request.
b7
b6
b5
b4
b3
b2
b1
b0
b7: Monday
b6: Tuesday
b5: Wednesday
b4: Thursday
b3: Friday
b2: Saturday
b1: Sunday
b0: unused
Example: If value "1111 1110" is set, the DHW will be
started each and every day.
4. Anti-Legionella DOW
Anti-legionella start request day of week.
b7
b6
b5
b4
b3
b2
b1
b0
b7: Monday
b6: Tuesday
b5: Wednesday
b4: Thursday
b3: Friday
b2: Saturday
b1: Sunday
b0: unused
Example: If value "1000 0000" is set, the Anti-Legionella
will be requested every Monday
5. Summer mode delay
The summer mode is set when the Summer Mode
switch is closed.
Summer Mode is set to "On" if OAT is above
Summer Mode OAT Threshold
[sum_oat] for at
least the period of a given delay (sum_on).
Summer Mode is reset if OAT goes below
Summer
Mode OAT Threshold
[sum_oat] minus 2 K for at
least the period of a given delay (sum_off).
6. DHW tank sensor type
0 = DHW Thermostat (thermal switch)
1 = DHW Sensor (thermistor 10 KΩ)
2 = DHW Sensor (thermistor 5 KΩ)
3 = DHW Sensor (thermistor 3 KΩ)
7. DHW tank delta T
DHW mode is requested if Tank Water Temperature
goes below DHW Setpoint [dhw_stp] minus DHW
Tank Delta T [dhw_dt].
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...