Monobloc Outdoor Unit Service Manual
115
10.1.4.2. Quick Test Table
Access type: Read-only (force is possible)
TABLE NAME: QCK_TEST, PIC Table Type: 12H, instance 2
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
321
QCK_ENA
No / Yes
No
-
Quick Test enable
322
_HP_TEST
0 to 8
0
-
HP Switch Test
1
323
_RAT_MOD
0 to 4
0
-
Rating Mode
2
324
_RAT_FRQ
-120 to 120
0
Hz
Rating Frequency
325
_FAN_LOW
0 to 999
0
rpm
Lower Fan Speed
326
_FAN_UPP
0 to 999
0
rpm
Upper Fan Speed
327
_PMV_POS
0 to 999
0
-
PMV Position
331
_PMP
0 to 100
0
%
Water Pump Speed
332
_EXH_HTR
Off / On
Off
-
Exchanger Elec. Heater
333
_ADD_PMP
Off / On
Off
-
Additional Pump
334
_SPR_REL
Off / On
Off
-
Spare Relay (KS)
335
_DHW_VLV
Off / On
Off
-
DHW Diverting Valve
336
_BOILER
Off / On
Off
-
Boiler or EH1
337
_CUSTDO8
Off / On
Off
-
Customized DO #8
338
_CUSTDO9
Off / On
Off
-
Customized DO #9
339
_HP_MAX
xxx.x
0.0
PSI
Maximum High Pressure
1. HP Switch Test
0 = HP Test Off
1 = HP Test Requested
2 = HP Test in Progress
3 = HP Test OK
4 = HP Test Failed due to timeout
5 = HP Test Failed due to Flow Switch Failure
6 = HP Test Failed due to Low Water Temperature
7 = HP Test Failed due to Inverter Failure
8 = HP Test failed due to high TL temperature
The HP Switch test can be launched if QCK_ENA is set
to “Yes” and current _RAT_MOD is 0 (Off Mode).
The goal of the HP Switch Test is to open the HP Switch.
The way to do it is to start in Cool Mode at 65 Hz, to stop
the fans, then wait for the pressure to increase until the
Pressure Switch opens.
2. Rating Mode
0 = Rating Off
1 = Rating Cool (set frequency with _RAT_FRQ
parameter)
2 = Rating Heat (set frequency with _RAT_FRQ
parameter)
3 = Ramp Cool (_RAT_FRQ corresponds to the change
rate Hz/min, ramp up if positive, ramp down if negative).
4 = Ramp Heat (_RAT_FRQ corresponds to the change
rate Hz/min, ramp up if positive, ramp down if negative).
NOTE
The Rating Mode is implemented for test purpose. When
the Rating Mode is active, Water Control Point is ignored
by the control.
The Ramp-up and Ramp-down Modes are implemented
for test purpose (Lab tests, etc.). When the Rating Mode
is active, Water Control Point is ignored by the control.
The pump is forced to run during the rating mode.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...