Related parameters for heating climatic curve control (predefined and custom):
Par.No
Description
Range
Default
402
Heat sleep offset – (hwunooff): (K)
-10.0 ~ 0.0
0.0
403
Heat away offset – (hwecooff): (K)
-10.0 ~ 0.0
-5.0
412
Heat curve max. set-point offset – (hcurvoff): (K)
-5.0 ~ 5.0
0.0
581
Heat clim curve select – (ht_curv)
-1 ~ 12
-1
582
Heat minimum OAT – (ht_min_a): (°C)
-30.0 ~ 10
-7.0
583
Heat maximum OAT – (ht_max_a): (°C)
10.0 ~ 30.0
20.0
584
Heat min. water set-point – (ht_min_w): (°C)
20.0 ~ 40.0
20.0
585
Heat max. water set-point – (ht_max_w): (°C)
30.0 ~ 60.0
38.0
8.2.14.
Summer mode control
The summer mode control is automatically enabled based on the current outdoor air temperature (OAT). When the
summer mode is activated the system is prevented from operating in space heating mode.
Summer mode is enabled when:
•
OAT > summer mode OAT threshold temperature [P716]
AND
the summer mode ON delay [P717] time has
elapsed
OR
•
The summer switch input, using digital inputs DI#05 ~ DI#08, changes status from OPEN to CLOSED
Summer mode is disabled when:
•
OAT < summer mode OAT threshold temperature [P716] – 2K
AND
the summer mode OFF delay [P718] time
has elapsed
OR
•
The summer switch input, using digital inputs DI#05 ~ DI#08, changes status from CLOSED to OPEN
Related Parameters for summer mode control:
Par.No
Description
Range
Default
042
Summer mode – (sum_mode)
0 ~ 1
0
502~508* Customer switch (DI) configuration
0 ~ 8
0
716
Summer mode OAT threshold – (sum_oat): (°C)
15.0 ~ 30.0
20.0
717
Summer mode ON delay – (sum_ON): (hr)
0 ~ 12
5
718
Summer mode OFF delay – (sum_OFF): (hr)
0 ~ 12
5
*Parameter required depends on DI selected. For example if DI#05 is used for the summer switch function
then [P502] needs to be set to 8
Note:
i)
If OAT is not available (OAT sensor not configured or failed) then the summer mode control is reset
If the summer switch (SUMM_SW) is CLOSED then the summer mode is forced to “YES”
8.2.15.
Floor Drying Mode
The floor drying mode allows a gradual water temperature ramp-up, in heating mode, to dry the concrete floor used in
underfloor heating (UFH).
Using the software parameters it is possible to set the start and holding temperatures and the number of days for the
warm-up, ramp-up and hold periods.
At the end of the floor drying cycle the control is automatically STOPPED.
Example application for floor drying mode:
•
Drying starting set point [P595] = 20°C
•
Drying warm-up days [P596] = 3
•
Drying ramp-up days [P597] = 4
•
Drying hold-up days [P598] = 5
Heating home set point [P401] = 28
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...