Monobloc Outdoor Unit Service Manual
101
10.1.2.3. Compressor Configuration Table
Access type: Read/Write
TABLE NAME: CMP_CONF, PIC Table Type: 10H, instance 3
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
541
powr_lim
50 to 100
75
%
Power Limitation value
1
542
nght_lim
50 to 100
75
%
Night Limitation value
2
543
dhw_lim
50 to 100
100
%
DHW Limitation value
3
1.
Power limitation
The compressor frequency is limited to this percentage of
the maximum allowed frequency when the
Frequency
Reduction Mode
parameter [FREQ_RED] is set to “Yes”
(LOADFACT). It can be activated with the power limitation
switch.
2.
Night Mode limitation
The compressor frequency is limited to this percentage of
the maximum allowed frequency when the Night Mode is
active.
3.
DHW Mode limitation
The compressor frequency is limited to this percentage of
the maximum allowed frequency when running in
Domestic Hot Water Mode.
10.1.2.4. Pump Configuration Table
Access type: Read/Write
TABLE NAME: PMP_CONF, PIC Table Type: 10H, instance 4
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
560
flui_typ
1 to 2
1
-
Fluid Type
1
561
pmp_ext
No / Yes
No
-
External Main Pump Ctrl
2
562
flw_chko
No / Yes
Yes
-
Flow Checked if Pump Off
563
pmp_stck
No / Yes
Yes
-
Anti-sticking function
564
sampling
5 to 240
15
min
Pmp Sampling Time Stby
3
565
pmp_log
1 to 3
1
-
Main Pump Logic
4
566
vsp_log
0 to 1
1
-
Var Speed Pump Logic
5
567
vsp_min
19 to 50
19
%
Minimum Pump Speed
568
vsp_max
50 to 100
100
%
Maximum Pump Speed
569
dt_stp
2.0 to 20.0
5.0
^C
Water Delta T Setpoint
570
dt_kp
-10.000 to -0.001
-6.000
-
Delta T Proport. Gain
571
dt_ti
10 to 120
20
s
Delta T Integral Time
572
dt_ts
10 to 120
10
s
Delta T Sample Time
573
add_pmp
0 to 4
0
-
Additional Pump Logic
6
1. Fluid type
1 = Water (min. cooling setpoint is 5°C)
2 = Medium Brine (min. cooling setpoint is 0°C)
2. External Pump Control
This parameter is taken into consideration only when the
Factory Par. 804 is set to "0", i.e. internal pump is NOT
available.
If there is no internal pump on the unit, then the external
pump control can be enabled.
3. Pump sampling time
When the unit is in Standby ("satisfied" mode) and the
water sampling function is enabled ([P565] set to "2"),
then the pump is running every "X" minutes* (for 2
minutes) in order to get a correct measurement of Water
Control Temperature.
* The pump sampling frequency is determined by setting
this specific parameter [P564].
4. Main pump logic
This parameter is used to define the state of the pump in
Standby mode:
1 = Always On
2 = Water Sampling
(WUI local, On/Off according to Par.565)
3 = According to Space Temp
(WUI remote or IAT sensor as Thermostat)
5. Variable speed logic
0 = Adjustable speed (use "vsp_max" to set the fixed
speed)
1 = Speed controlled by the Water Delta T
6. Additional pump logic
This parameter defines the status of the additional pump
when the unit is in Standby:
0 = No additional Pump (no add. Pump logic active)
1 = Always On
2 = According to Space Temp (WUI remote)
3 = Always On, but Off when DHW is active
4 = According to Space Temp (WUI remote), but Off
when DHW is active
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...