The operation of the heating mode is determined by the temperature sensor located inside the remote
controller
•
The heating operation will start when:
[1]
Room Air Temperature < Air Set point [P421] – Air Delta Set point [P428]
•
The heating operation will continue until:
[2]
Room Air Temperature > Air Set point [P421] + Air Delta Set point [P428]
OR
[3]
Room Air Temperature > Air Set point [P421]
AND
current capacity is less than 10%
Related Parameters for Room Air Temperature Control:
Par.No
Description
Range
Default
421
Heat home set point – (hwoccstp): [°C]
12.0 ~ 34.0
19.0
422
Heat home offset – (hwunooff): [K]
-10.0 ~ 0.0
-2.0
423
Heat away offset – (hwecooff): [K]
-10.0 ~ 0.0
-4.0
428
Air delta set point – (deltastp)
0.2 ~ 1.0
0.5
521
User interface type – (ui-type)
0~3
0
8.2.4. Cooling Operation
•
Cooling control using water temperature:
The cooling operation is controlled by the system
Control Temperature
(CTRL_TMP) and the system
Control Point
(CTRL_PNT). The Control Temperature is measured by the leaving water temperature sensor (LWT) [P004].
To prevent the system short cycling, in cooling mode, the
Water Cool Hysteresis
[P411 parameter must be set.
The
Control Point
(CTRL_PNT) has to be set for each of the occupancy modes. This is achieved by applying an
offset to the
Control Point
(CTRL_PNT) set for the “HOME” mode. The offsets are applied by setting parameters
[P408 – Cool Sleep Offset] and [P409 – Cool Away Offset].
It is possible to select either water temperature or room air temperature controller using the same remote controller.
This is achieved by setting the
User Interface Type
[P521]
Control Point
Remote Inputs
[P521 = 1]
Leaving water temperature
Remote Controller (Air)
[P521 = 2]
Room air temperature
Remote Controller (water)
[P521 = 3]
Leaving water temperature
Control Temperature (CTRL_TMP) = leaving water temperature (LWT) [P004]
Control Point (CTRL_PNT) = set point temperature
Water Cool Hysteresis = [P411]
OFF
[3]
CTRL_PNT
(-) Cool Hysteresis
ON
Cooling Operation
(+) Cool Hysteresis
LWT
[1]
[2]
[1]
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...