Monobloc Outdoor Unit Service Manual
121
10.1.5.2. Air Setpoint Table
Access type: Read/Write
TABLE NAME: AIR_STP, PIC Table Type: 17H, instance 2
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
421
htoccstp
12.0 to 34.0
19.0
°C
Heat Home Setpoint
1
422
htunooff
-10.0 to 0.0
-2.0
^C
Heat Sleep Offset
1, 2
423
htecooff
-10.0 to 0.0
-4.0
^C
Heat Away Offset
1, 3
424
cloccstp
20.0 to 38.0
26.0
°C
Cool Home Setpoint
1
425
clunooff
0.0 to 10.0
2.0
^C
Cool Sleep Offset
1, 2
426
clecooff
0.0 to 10.0
4.0
^C
Cool Away Offset
1, 3
427
freezstp
6.0 to 12.0
6.0
°C
Home AntiFreeze Setpoint
4
428
deltastp
0.2 to 1.0
0.5
^C
Air Delta Setpoint
5
429
iat_fact
0.0 to 2.0
0.0
-
IAT Reset Factor
6
1. Occupancy modes
Occupancy Comfort Type
Home
Comfort
Sleep
Comfort
Away
Eco
2. Sleep offset
The offset applied to the Home setpoint.
3. Away offset
The offset applied to the Home setpoint.
4. Anti-freeze setpoint
This is the minimum room temperature that is allowed.
If room temperature drops below this setpoint, the unit will
start to operate in Heating mode.
5. Air delta setpoint
This parameter is used to determine whether the control
is in cooling or heating demand.
6. IAT reset factor
This parameter is used to determine the indoor air
temperature.
10.1.6.
POC tables
POC tables are used to control Follower units that are interconnected to operate in the same Header /
Follower assembly.
10.1.6.1. Follower 0 Status Table
Access type: Read-only
TABLE NAME: SLV0STAT, PIC Table Type: 615H, instance 1
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
1001
ewt
xx.x
-
°C
Entering Water Temp
1002
lwt
xx.x
-
°C
Leaving Water Temp
1003
mod_stat
0 to 101
-
-
System Mode Status
1
1004
alm
Normal/Alarm
-
-
Alarm Status
1005
cap_t
0 to 100
-
%
Total Capacity
1006
cap_ovr
0 to 204
-
-
Capacity Override
1007
pmp
0 to 100
-
%
Water Pump Speed
1008
pmp_ovr
-1 to 100
-
-
Pump Override
1009
flow_sw
Close/Open
-
-
Flow Switch Status
1010
freq_cur
0 to 120
-
Hz
Actual Compressor Freq
1011
wearfact
xxxxxxxx
-
-
Unit Wear Factor
2
1. System Mode Status
-1 = Disabled
0 = Off
1 = Cool
2 = Heat
3 = unused
4 = DHW (Heat)
5 = Booster Cooling
6 = Booster Heating
7 = Defrost
8 = Purge
9 = Drying
20 = Home Anti-Freeze
21 = Cool Satisfied
22 = Heat Satisfied
24 = DHW Satisfied
29 = Drying Satisfied
100 = Not Responding
101 = Failed
2. Unit wear factor
The unit wear factor is calculated based on the number of
operating hours of the compressor as well as the number
of starts of the compressor
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...