Monobloc Outdoor Unit Service Manual
70
9.
Method of defect analysis
9.1.
Matters to be confirmed first
9.1.1.
Initial check items
Check item
Action
Nothing is displayed on the RC.
• Check whether power is supplied.
• Is the circuit breaker switch turned on?
Time indication is blinking on the RC.
• Date/time setting is not made.
• Set date and time.
Room is not cooled or heated.
• Is scheduled operation set?
• Check whether scheduled operation is set on the RC.
• Is occupancy set?
• Check the setting on the RC.
• Is the air to water heat pump operating according climatic curves?
• In climatic curve mode, the target value is set automatically
according to the outdoor unit temperature.
• If required adjust the climatic curves.
Hot water is not supplied.
• Is the main water supply cock closed?
• Check valves.
• Are you using too much hot water?
• If hot water usage exceeds the storage capacity, there is a risk
that the set hot water temperature cannot be achieved.
9.1.2.
Check the power supply voltage
Check that the power supply voltage is AC360-440 V (3 phase). If the power supply voltage is not in this range, it
may not operate normally.
9.1.3.
Check for any miss-wiring of the connection cables
Make sure any cables connected to the Monobloc are in the correct positions.
9.1.4.
About the installation of the temperature sensor
If each sensor is removed due to the replacement of the water heat exchange or inverter board, or the replacement of
the refrigeration cycle parts, make sure to put the sensor back to the position where it was before.
• Each sensor position has a marking. Make sure to put it back to the exact position.
• Make sure to install it with a sensor holder so that the temperature sensing part of the sensor and the
straight part of the copper piping are attached with each other tightly.
• If the installation of the sensor is incomplete or the installed position is wrong, it will not perform a normal
control operation and may cause a defect such as a malfunction of the equipment or an occurrence of an
abnormal sound, etc.
9.2.
Non-defective operation (program operation – no error code)
In order to control the heat pump unit, there are the following operations as the built-in program operations in the
microcomputer. If a claim occurs about the operation, please confirm whether it falls under any of the contents in the
following table.
If it does, please understand that the symptom is not a defect of the equipment, and it is an operation necessary for
the control and maintenance of the heat pump unit.
No.
Operation of the heat pump system
Explanation
1
The compressor sometimes does not operate even within the
range of compressor “ON”.
The compressor does not operate during the operation of the
compressor reboot timer (3 min). Even after the power
activation, the compressor reboot timer continues to be active.
2
During the hot water supply or heating operation, without
reaching the set temperature, the compressor operation
frequency stays at a frequency of less than the maximum Hz or
lowers down.
It may be caused by the high temperature release control
(release protection control by the temperature of the water
heat exchanger) or the current release control, or the high
pressure release control.
3
The “Stop” operation on the remote controller will not stop the
circulating pump. (The same for hot water supply, heating and
cooling)
In order to deal with the temperature increase in the heat
exchanger after stopping, the operation continues for 1 min
after the compressor is stopped.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...