Monobloc Outdoor Unit Service Manual
66
8.4.6. Defrost logic
•
In heating operation, defrost operation is performed when TE sensor temperature satisfies any
condition in A zone to D zone.
•
The defrost operation is immediately finished if TE sensor temperature has become 12°C or more,
or it also is finished when condition of 7°C < TE < 12°C has continued for 1 minute. The defrost
operation is also finished when defrost operation has continued for 10 minutes even if TE sensor
temperature has become 7°C or lower.
•
After defrost operation has finished, the unit switches back in heating mode.
8.4.6.1. Defrost mode on 17kW unit
* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in
memory as TE0.
A zone
Status [TE0-TE > 3] continues for 20 seconds.
B zone
Defrost operation is performed in this zone when [TE0-TE > 3] continues for 20 seconds.
C zone
Defrost operation is performed when this zone continues for 20 seconds.
D zone
Defrost operation is performed when this zone continues for 20 seconds.
8.4.6.2. Defrost mode on 21kW unit
* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in
memory as TE0.
When To is normal
When To is abnormal
A zone
Status [(TEO-TE) – (ToO-To
) ≥ 3] continues
for 20 secs
Status [TEO- TE
≥ 3] continues for 20 secs
B zone
Status [(TEO-TE) – (ToO-To
) ≥ 2] continues
for 20 secs
Status [TEO-TE
≥ 2] continues for 20 secs
C zone
Status [TE
≤ 23°C] continues for 20 seconds
D zone
When compressor operation status TE < 2°C is calculated for d minutes
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...