Monobloc Outdoor Unit Service Manual
53
•
Fixed Speed Pump Option (pmp_type = 1)
The fixed speed pump option is fitted in the factory. ON / OFF control of the pump is available from the NHC board
via an internal contactor as shown below:
The speed of the pump can be adjusted using a manual speed selector switch located on the pump electrical box.
There are 3 pump speeds available on the fixed speed pump.
The following table shows the minimum and maximum pressures required in the hydronic circuit for correct operation
of a unit with the fixed speed pump option fitted:
Hydraulic circuit
Minimum pressure at the
suction of the pump to avoid
the cavitation phenomena.
Maximum pressure at the
suction of the pump before
the opening of the water relief
valve *
Fixed speed hydronic
module
50kPa (0.5 bar)
300 kPa (3 bar)
To ensure the correct and safe operation of the system a minimum water flow rate must be maintained throughout the
hydronic circuit. If the minimum flow rate is not maintained then the contacts on the flow switch, incorporated into the
fixed speed pump hydronic module, will OPEN and the system will STOP due to a low water flow (alarm code 32 – the
system will STOP after 5 attempts to run).
The minimum flow rates for the ESTIA Monobloc outdoor units, fitted with the fixed speed hydronic module, are
shown below:
RUA-CP170 / 2101H units with fixed speed hydronic module
Minimum water flow rate, l/s Maximum water flow rate, l/s
17
0.45
1.4
21
0.57
1.6
Fixed speed pump characteristic (static pressure v water flow rate):
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...