10.1.5.
Setpoint tables
Setpoint tables provide information on temperatures to be achieved, including the reset adjustment.
10.1.5.1. Water Setpoint Table
Access type: Read/Write
TABLE NAME: WAT_STP, PIC Table Type: 17H, instance 1
PAR.
NAME
RANGE
DEFAULT
UNIT
DESCRIPTION
401
hwoccstp
20.0 to 60.0
45.0
°C
Heat Home Setpoint
1
402
hwunooff
-10.0 to 0.0
0.0
^C
Heat Sleep Offset
3
403
hwecooff
-10.0 to 0.0
-5.0
^C
Heat Away Offset
4
404
dhwecstp
20.0 to 60.0
45.0
°C
DHW Eco Setpoint
405
leg_stp
50.0 to 60.0
60.0
°C
DHW Anti-Legionella Stp
406
dhw_stp
30.0 to 60.0
50.0
°C
DHW Setpoint
407
cwoccstp
0.0
to 18.0
12.0
°C
Cool Home Setpoint
2
408
cwunooff
0.0 to 10.0
0.0
^C
Cool Sleep Offset
3
409
cwecooff
0.0 to 10.0
0.0
^C
Cool Away Offset
4
410
hw_hyst
0.5 to 2.0
1.0
^C
Heat Hysteresis
411
cw_hyst
0.5 to 2.0
0.5
^C
Cool Hysteresis
5
412
hcurvoff
-5.0 to 5.0
0.0
^C
Heat Curv Max Stp Offset
413
ccurvoff
-5.0 to 5.0
0.0
^C
Cool Curv Min Stp Offset
1. Heating water setpoints
These setpoints are used when Heating Climatic Curve
Select [ht_curv] is set to "-1" (Par.581 in CLIMCURV).
2. Cooling water setpoints
These setpoints are used when Cooling Climatic Curve
Select [cl_curv] is set to "-1" ([P586] in CLIMCURV).
3. Sleep offset
The offset applied to the Home Setpoint.
4. Away offset
The offset applied to the Home Setpoint.
5. Hysteresis
The minimum threshold to switch off the compressor is
limited to
MinimumCoolingSetpoint - 0.5 K
(even if
CRTL_PNT is minimum and hysteresis is configured to 2
K).
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...