Monobloc Outdoor Unit Service Manual
142
13. Replacement of the service PC board
13.1.
Inverter Box Replacement
Tools:
Screwdriver
Steps:
1. Perform the works of (12.1, 12.2 and 12.3)
2. Disconnect all cables of the inverter box in being careful of wire locations
-
TL sensor
-
TS sensor
-
TD sensor
-
TO sensor
-
TE sensor
-
2 fans
-
Four way valve
-
Two way valve
-
HP switch
-
Thermal cut off of compressor
-
PMV’s (one for 17kW and two for 21kW)
-
LP sensor
-
Wires 1 / 2 / 3 connected of NHC board
-
Power L1 / L2 / L3 / Neutral / Earth
-
Power of compressor (directly on the compressor = 3 wires)
3. Remove six screws which maintain the inverter box
4. Remove the inverter box (to remove it, lift up it)
For 5 minutes after the power is turned off, do not disassemble the inverter to prevent an
electric shock
Compressorpower of 21kW
Compressorpower of 17kW
Fans
NHC connections
Powersupply
Other connections
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...