Monobloc Outdoor Unit Service Manual
57
Related parameters associated with pump control:
Par.No
Description
Range
Default
560
Fluid type – (flui_typ)
1 ~ 2
1
561
External main pump control – (pmp_ext)
0 ~ 1
0
562
Flow checked if pump off – (flw_chko)
0 ~ 1
1
563
Anti-sticking function – (pmp_stck)
0 ~ 1
1
564
Pump sampling time standby – (sampling): (min)
5 ~ 240
15
565
Main pump logic – (pmp_log)
1 ~ 3
1
566
Variable speed pump logic – (vsp_log)
0 ~ 1
1
567
Minimum pump speed – (vsp_min): (%)
19 ~ 50
19
568
Maximum pump speed – (vsp_max): (%)
50 ~ 100
100
569
Water
∆
T setpoint – (dt_stp): (K)
2.0 ~ 20.0
5.0
570
∆
T proportional gain – (dt_kp)
-10.000 ~ -0.001
-6.000
571
∆
T integral time – (dt_ti)
10 ~ 120
20
572
∆
T sample time – (dt_ts)
10 ~ 120
10
573
Additional pump logic – (add_pmp)
0 ~ 4
0
8.2.17.
Flow Switch Control
A paddle flow switch is installed into the water pipe work of the unit to warn of low water flow within the system.
The flow switch limitations are as follows:
Flow switch setpoint
Flow rate
Setpoint increasing flow “ON”
0.28 l/s
Setpoint decreasing flow “OFF’”
0.24 l/s
After 5 retries of start-up of pump, with the paddle flow switch, which stays opened, the alarm 32 activates.
8.3.
Override List
To know the override status of unit, refer to parameters:
•
Capacity override : [P064]
•
System Mode Override: [P047]
•
Pump override: [P081]
•
Backup override: [P091]
8.3.1. SYSTEM MODE OVERRIDE [P047]
In certain cases, the control system may override the currently running operating mode in order to
optimize the performance of the unit.
The control system may employ the following overrides:
#
Override
Remarks
0
No override
Unit runs normally
1
Home Anti-Freeze
Unit is running in Booster Heat Mode for Home Anti-Freeze protection
2
Water Loop Anti- Freeze
Unit is running in Booster Heat Mode for Water Loop Anti-Freeze protection
10
Loadshed Requested
Unit shall be stopped as soon as possible
11
Off Peak
Compressor and electric heaters are not allowed to run
12
Solar Production
Unit is not allowed to run in Heat Mode or DHW Mode because hot water is
produced by a solar system.
13
Summer mode
Unit is not allowed to run in Heat Mode because summer mode is active.
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...