A-63
Appendices
CP2E CPU Unit Software User’s Manual(W614)
A-2 A
u
xil
iar
y Area A
llocation
s b
y
Ad
dress
App
A-2-1 Read-only W
o
rds
A99
00
UM Read Protection
Status
Indicates whether all of the ladder
programs in the PLC are
read-protected.
ON: UM read-
protected.
OFF: UM not
read-protected
Retained
Retained
When
protection is
set or cleared
A100
to A199
---
Error Log Area
When an error has occurred, the error
code, error contents, and error's time
and date are stored in the Error Log
Area. Information on the 20 most
recent errors can be stored.
Each error record occupies 5 words;
the function of these 5 words is as
follows:
First word: Error code (bits 0 to 15)
First word + 1: Error contents (bits 0 to
15)
First word + 2: Minutes (upper byte),
Seconds (lower byte)
First word +
3
: Day of month (upper
byte), Hours (lower byte)
First word + 4: Year (upper byte),
Month (lower byte)
Note 1
Errors generated by FAL(006)
and FALS(007) will also be
stored in this Error Log.
2
The Error Log Area can be
reset from the CX-Program-
mer.
3
If the Error Log Area is full (20
records) and another error
occurs, the oldest record in
A100 to A104 will be cleared,
the other 19 records are
shifted down, and the new
record is stored in A195 to
A199.
4
In an E
-type CPU Unit, the
data will be for 1:01.01 on Sun-
day January 1, 2001.
Error code
Error contents:
Address of Aux. Area
word with details or
0000 hex if there is
no related word.
Seconds: 00 to 59,
BCD
Minutes: 00 to 59,
BCD
Hours: 00 to 2
3
, BCD
Day of month: 01 to
3
1, BCD
Month: 01 to 12, BCD
Year: 00 to 99, BCD
Retained
Retained
Refreshed
when error
occurs.
A500.14
A
3
00
A400
A200
11
First Cycle Flag
ON for one cycle after PLC operation
begins (after the mode is switched from
PROGRAM to RUN or MONITOR, for
example).
ON for the first cycle
ON
Cleared
---
12
Step Flag
ON for one cycle when step execution
is started with STEP. This flag can be
used for initialization processing at the
beginning of a step.
ON for the first cycle
after execution of
STEP.
Cleared
Cleared
---
14
Task Started Flag
When a task switches from WAIT or INI
to RUN status, this flag will be turned
ON within the task for one cycle only.
Note
The only difference between this
flag and A200.15 is that this flag
also turns ON when the task
switches from WAIT to RUN sta-
tus.
ON: ON for first cycle
(including
transitions from
WAIT and IN)
OFF: Other
Cleared
Cleared
---
15
First Task Startup Flag
ON when a task is executed for the first
time. This flag can be used to check
whether the current task is being
executed for the first time so that
initialization processing can be
performed if necessary.
ON: First execution
OFF: Not executable
or not being
executed for the
first time.
Cleared
Cleared
---
Address
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words
Bits
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......