16 Other Functions
16-12
CP2E CPU Unit Software User’s Manual(W614)
Precautions for Safe Use
Power Interruptions during Backup
The BKUP indicator on the front of the CPU Unit will be lit when DM Area data is being saved to
the built-in Flash Memory.
Do not turn OFF the power supply to the PLC while the indicator is lit. If the power supply to the
PLC is turned OFF while the BKUP indicator is lit, data will not be backed up. In this case, the
DM Backup Restore Failed Flag (A751.11) will turn ON when the power supply is turned ON
again. Therefore, the backup data will not be restored to the DM Area. Transfer the data from the
CX-Programmer to the DM Area again.
Precautions for Correct Use
Precautions for Correct Use
•
To prevent operation from starting if the DM backup data is not restored correctly when the
power supply is turned ON, insert the following instructions into the ladder program to gener-
ate a fatal error.
•
To ensure concurrency between DM backup data and the contents of the DM Area in the I/O
memory, use exclusive processing in the ladder program so that contents of the DM Area
words in the I/O memory that are set to be backed up are not changed during a backup
operation.
•
Data can be written up to 100,000 times to the built-in Flash Memory. Data cannot be written
once this limit is exceeded. If writing fails, A
3
15.15 (Backup Memory Error Flag) will turn ON.
Additional Information
Confirming Completion of DM Area Backup
If user programs or the parameter area is being saved to the backup memory using operations
from the CX-Programmer, the backup operation will not be executed immediately even if
A751.15 (DM Backup Save Start Bit) is turned ON. A751.14 (DM Backup Save Flag) will remain
ON during this time and turn OFF when the DM backup operation has been completed. You can
confirm the completion of DM backup by checking to see if the DM Backup Save Flag (A751.14)
has been turned OFF.
A751.11
DM Back
u
p Restore Failed Flag
Generates a
u
ser-defined
fatal error
FALS
10
#0000
DM B
a
ck
u
p
Sa
ve Fl
a
g
A751.14
Progr
a
mming to ch
a
nge the
content
s
of DM Are
a
word
s
th
a
t
a
re
s
et to
b
e
ba
cked
u
p
DM Are
a
word
s
th
a
t
a
re
s
et to
b
e
ba
cked
u
p will
not
b
e ch
a
nged d
u
ring
a
ba
ck
u
p oper
a
tion to
en
su
re conc
u
rrency
b
etween DM
ba
ck
u
p d
a
t
a
a
nd word
s
in the DM Are
a
in the I/O memory.
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......