12-9
12 Pulse Outputs
CP2E CPU Unit Software User’s Manual(W614)
1
2-1 Over
vie
w
12
12
-1-2
Flo
w
of Oper
ation
z
Connections for Pulse Output 1
z
Connections for Pulse Output 2 (Only for N30/40/60 CPU Units)
Terminal block
Addresses
Signal
Origin search
Terminal
block
label
Terminal
number
Operating mode 0 Operating mode 1 Operating mode 2
CIO 100
01
CIO 100.01 Stored in A27
8
and A279
Pulse
Connect to Servo Drive
’
s pulse input (PULS).
0
3
CIO 100.0
3
Direction
Connect to Servo Drive
’
s direction input (SIGN).
Normal input
The external signal must be
received as an input and
the input status must be
written to A541.0
8
in the
ladder program.
CW limit
sensor
Connect sensor to a normal input terminal.
Normal input
The external signal must be
received as an input and
the input status must be
written to A541.09 in the
ladder program.
CCW limit
sensor
Connect sensor to a normal input terminal.
CIO 0
05
CIO 0.05
Origin prox-
imity input
Connect to sensor for N14 CPU Unit.
07
CIO 0.07
Origin input
Connect to open-
collector output
from sensor or
other device.
Connect to the
phase-Z signal
from the Servo
Drive.
Connect to the
phase-Z signal
from the Servo
Drive.
11
CIO 0.11
Origin prox-
imity input
Connect to sensor for N20/
3
0/40/60 CPU Unit.
CIO 100
05
CIO 100.05
Error counter
reset output
Not used.
Connect to error counter reset (ECRST)
of the Servo Drive.
Normal input
The external signal must be
received as an input and
the input status must be
written to A541.10 in the
ladder program.
Positioning
completed
input
Not used.
Connect the Posi-
tioning Completed
Signal (INP) from
the Servo Drive to
a normal input ter-
minal.
Terminal block
Addresses
Signal
Origin search
Terminal
block
label
Terminal
number
Operating mode 0 Operating mode 1 Operating mode 2
CIO 101
00
CIO 101.01 Stored in A52
and A5
3
.
Pulse
Connect to Servo Drive
’
s pulse input (PULS).
02
CIO 101.02
Direction
Connect to Servo Drive
’
s direction input (SIGN).
Normal input
The external signal must be
received as an input and
the input status must be
written to A542.0
8
in the
ladder program.
CW limit
sensor
Connect sensor to a normal input terminal.
Normal input
The external signal must be
received as an input and
the input status must be
written to A542.09 in the
ladder program.
CCW limit
sensor
Connect sensor to a normal input terminal.
CIO 0
0
8
CIO 0.0
8
Origin input
Connect to open-
collector output
from sensor or
other device.
Connect to the
phase-Z signal
from the Servo
Drive.
Connect to the
phase-Z signal
from the Servo
Drive.
CIO 1
00
CIO 1.00
Origin prox-
imity input
Connect to sensor
CIO 100
06
CIO 100.06
Error counter
reset output
Not used.
Connect to error counter reset (ECRST)
of the Servo Drive.
Normal input
The external signal must be
received as an input and
the input status must be
written to A542.10 in the
ladder program.
Positioning
completed
input
Not used.
Connect the Posi-
tioning Completed
Signal (INP) from
the Servo Drive to
a normal input ter-
minal.
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......