12 Pulse Outputs
12-18
CP2E CPU Unit Software User’s Manual(W614)
Precautions for Correct Use
Precautions for Correct Use
The absolute pulse cannot be specified with the origin undefined. Please specify them when the
origin is defined by performing the origin searches.
Additional Information
The origin position is undefined in the following case. Please define the origin position by per-
forming the origin searches again.
•
When the pulse output reset flag is turned ON
•
When the RUN or MONITOR mode is changed to the PROGRAM mode
When the start input (CIO 0.00) goes ON, this example program outputs 600,000 pulses from pulse
output 1 to turn the motor.
PLS2
z
PLC Setup
There are no settings that need to be made in the PLC Setup.
12-2-3 Application Example
Specifications and Operation
Applicable Instructions
Preparations
0.00
200Hz/4ms
100Hz
50,000 Hz
300Hz/4ms
Target fre
qu
ency
Starting fre
qu
ency
Start inp
u
t
Acceleration
rate
Nu
m
b
er of o
u
tp
u
t
p
u
lses
600,000 p
u
lses
Deceleration rate
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......