A-65
Appendices
CP2E CPU Unit Software User’s Manual(W614)
A-2 A
u
xil
iar
y Area A
llocation
s b
y
Ad
dress
App
A-2-1 Read-only W
o
rds
A270
to A271
---
High-speed Counter 0
PV
Contains the PV of high-speed counter
0. A271 contains the upper 4 digits and
A270 contains the lower 4 digits.
Cleared
Cleared
•
Refreshed
each cycle
during the
overseeing
processes.
•
Refreshed
when PRV
instruction is
executed to
read the PV.
•
Refreshed
when INI
instruction is
executed.
A272
to A27
3
---
High-speed Counter 1
PV
Contains the PV of high-speed counter
1. A27
3
contains the upper 4 digits and
A272 contains the lower 4 digits.
Cleared
Cleared
•
Refreshed
each cycle
during the
overseeing
processes.
•
Refreshed
when PRV
instruction is
executed to
read the PV.
•
Refreshed
when INI
instruction is
executed.
A274
00
High-speed Counter 0
Range 1 Comparison
Condition Met Flag
These flags indicate whether the PV is
within the specified ranges when
high-speed counter 0 is being operated
in range-comparison mode.
ON: PV in range
OFF: PV not in range
Cleared
Cleared
•
Refreshed
each cycle
during the
overseeing
processes.
•
Refreshed
when PRV
instruction is
executed to
read the
results of
range com-
parison.
•
Refreshed
when range
comparison
table is reg-
istered.
01
High-speed Counter 0
Range 2 Comparison
Condition Met Flag
02
High-speed Counter 0
Range
3
Comparison
Condition Met Flag
0
3
High-speed Counter 0
Range 4 Comparison
Condition Met Flag
04
High-speed Counter 0
Range 5 Comparison
Condition Met Flag
05
High-speed Counter 0
Range 6 Comparison
Condition Met Flag
0
8
High-speed Counter 0
Comparison
In-progress Flag
This flag indicates whether a
comparison operation is being
executed for high-speed counter 0.
ON: Being executed
OFF: Stopped
---
Cleared
Refreshed
when
comparison
operation
starts or stops.
09
High-speed Counter 0
Overflow/Underflow
Flag
This flag indicates when an overflow or
underflow has occurred in the
high-speed counter 0 PV. (Used with
the linear mode counting range only.)
ON: Overflow or
underflow
OFF: Normal
Cleared
Cleared
•
Refreshed
when an
overflow or
underflow
occurs.
•
Refreshed
when PV is
changed.
Address
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words
Bits
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......