14 Serial Communications
14-34
CP2E CPU Unit Software User’s Manual(W614)
z
Related Auxiliary Area Bits and Words
Serial Port1/Built-in RS-232C Port
Name
Address
Details
Read/write
Refresh timing
Serial Port 1/Built-in
RS-2
3
2C Port Com-
municating with
Polled Unit Flags*
A
3
9
3
.00 to
A
3
9
3
.07
When the serial port 1 or built-in
RS-2
3
2C port is being used in NT
link mode, the bit corresponding to
the Unit performing communica-
tions will be ON. Bits 00 to 07 corre-
spond to unit numbers 0 to 7,
respectively.
ON: Communicating
OFF: Not communicating
Read
•
Cleared when power is turned ON.
•
Turns ON the bit corresponding to the unit number
of the Polled Unit that is communicating via the
serial port 1 or built-in RS-2
3
2C port in NT link
mode or Serial PLC Link mode.
•
Bits 00 to 07 correspond to unit numbers 0 to 7,
respectively.
Serial Port 1/Built-in
RS-2
3
2C Port
Restart Bit
A526.00
Turn ON this bit to restart the serial
port 1 or built-in RS-2
3
2C port.
Read/write
•
Cleared when power is turned ON.
•
Turn ON to restart the serial port 1 or built-in RS-
2
3
2C port.
Note
The bit is automatically turned OFF by the
system when restart processing has been
completed.
Serial Port 1/Built-in
RS-2
3
2C Port Error
Flags
A52
8
.00 to
A52
8
.07
When an error occurs at the serial
port 1 or built-in RS-2
3
2C port, the
corresponding error bit is turned
ON.
Bit 0: Not used.
Bit 1: Not used.
Bit 2: Parity error
Bit
3
: Framing error
Bit 4: Overrun error
Bit 5: Timeout error
Bit 6: Not used.
Bit 7: Not used.
Read/write
•
Cleared when power is turned ON.
•
When an error occurs at the serial port 1 or built-in
RS-2
3
2C port, the corresponding error bit is turned
ON.
•
The flag is automatically turned OFF by the system
when the serial port 1 or built-in RS-2
3
2C port is
restarted.
•
In NT link mode, only bit 05 (timeout error) is
enabled.
•
In Serial PLC Link mode, only the following bits are
enabled.
Errors at the Polling Unit:
Bit 05: Timeout error
Errors at Polled Units:
Bit 04: Overrun error
Bit 0
3
: Framing error
Bit 02: Parity error
Note
If the error occurred in Serial PLC link mode,
the console will retry before communication
establish. Rehabilitation of the communica-
tions is no need for port restart. If user elimi-
nates error, the communication will
automatically establish between console and
servo.
However, error flag will be saved as the
record. If you want to clear the error flag,
please restart port.
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......