15-47
15 Ethernet
CP2E CPU Unit Software User’s Manual(W614)
15-5 Soc
ket Ser
vic
es
15
15-5-6 D
ata Memor
y
Are
a Alloca
tions
UDP Socket Receive Request
UDP Socket Send Request
UDP Socket Close Request
Response code
Meaning
0000
Normal end
0
3
02
CPU Unit error; cannot execute.
1100
Number of bytes to receive is not in allowable range.
1101
The area designation of the Send/Receive Data Address is not inallowable range.
110
3
The bit number in the Send/Receive Data Address is not 00.
110C
Request Switch turned ON during other processing.
220F
Specified socket is already processing a receive request.
2210
The specified socket is not open.
2211
Unit is busy; cannot execute service.
2607
Specified Socket Service Parameter Area is already being used foranother socket.
00
8
0
Receive request timed out.
00
8
1
The specified socket was closed during reception processing.
Response
code
Meaning
0000
Normal end
0
3
02
CPU Unit error; cannot execute.
1100
Number of bytes to send is not in allowable range or the remote IPaddress is 0.
1101
The area designation of the Send/Receive Data Address is not inallowable range.
110
3
The bit number in the Send/Receive Data Address is not 00.
110C
Request Switch turned ON during other processing.
220F
Specified socket is already processing a send request.
2210
The specified socket is not open.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used foranother socket.
00
3
E
Internal buffer cannot be obtained due to high reception traffic (ENOBUFS).
004C
The network ID is incorrect or the remote IP address is incorrect(EADDRNOTAVAIL)
004E
The network ID is not in the IP router table, router settings are incorrect, or the remote IP
address is incorrect (ENETUNREACH).
00
8
1
The specified socket was closed during send processing.
Response
code
Meaning
0000
Normal end
0
3
02
CPU Unit error; cannot execute.
2210
The specified socket is not open.
2607
Specified Socket Service Parameter Area is already being used foranother socket.
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......