B
Diagnostic messages
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
279
Error group 90
Internal error
No.
Reaction
Message
Code
90-4
5080h
SD-ADU synchronisation error after start
PSoff
Cause
SD-ADU (hardware) not synchronous after starting. During opera
tion, the SD-ADUs for the resolver signals continue running with
strict synchronisation once they have been initially started syn
chronously. The SD-ADUs could not be started at the same time
during that initial start phase.
Measure
Switch on the device again (24 V). If the error occurs again, the
hardware is faulty.
90-5
5080h
SD-ADU not synchronous
PSoff
Cause
SD-ADU (hardware) not synchronous after starting. During opera
tion, the SD-ADUs for the resolver signals continue running with
strict synchronisation once they have been initially started syn
chronously. This is checked continually during operation and an
error is triggered if appropriate.
Measure
Possibly massive EMC coupling.
Switch on the device again (24 V). If the error occurs again, the
hardware is faulty.
90-6
5080h
IRQ0 (current controller): Trigger error
PSoff
Cause
The output stage is not triggering the software IRQ, which then
operates the current regulator. Very likely to be a hardware error
on the board or in the processor.
Measure
Switch on the device again (24 V). If the error occurs again, the
hardware is faulty.
90-9
5080h
Illegal firmware version
PSoff
Cause
A beta version compiled for the debugger was loaded regularly.
Measure
Check the firmware version, and update the firmware if neces
sary.
Error group 91
Initialisation error
No.
Code
Message
Reaction
91-0
6000h
Internal initialising error
PSoff
Cause
Internal SRAM too small for the compiled firmware. Can only occur
with beta versions.
Measure
Check the firmware version, and update the firmware if neces
sary.