Diagnostic messages
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
275
Error group 72
PROFINET (only CMMP-AS-...-M3)
No.
Reaction
Message
Code
72-3
-
PROFINET: Invalid IP configuration
configurable
Cause
An invalid IP configuration was entered in the interface. The inter
face cannot start with this configuration.
Measure
Parameterise a permissible IP configuration via FCT.
72-4
-
PROFINET: Invalid Device name
configurable
Cause
A PROFINET device name was assigned with which the controller
cannot communicate with the PROFINET (character specification
from PROFINET standard).
Measure
Parameterise a permissible PROFINET device name via FCT.
72-5
-
PROFINET: Module faulty
configurable
Cause
Interface CAMC-F-PN faulty.
Measure
Replace interface.
72-6
-
PROFINET: Indication invalid/not supported
configurable
Cause
A message was issued by the PROFINET interface that is not sup
ported by the motor controller.
Measure
Please contact Technical Support.
Error group 73
PROFINET (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
73-0
-
PROFIenergy: State not possible
configurable
Cause
An attempt was made in a positioning motion to place the control
ler in the energy-saving status. This is only possible at rest. The
drive does not take on the status and continues to travel.
Measure
–
Error group 78
NRT communication (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
78-0
-
NRT frame can't be send
configurable
Cause
NRT Frame can't be send because of too much bus load.
Measure
Switch off or disconnect other bus devices during parametrisa
tion.
Error group 80
IRQ overflow
No.
Code
Message
Reaction
80-0
F080h
Overflow current controller IRQ
PSoff
Cause
The process data could not be calculated in the set current/speed/
position interpolator cycle.
Measure
Please contact Technical Support.