5
Setting parameters
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
135
Object 6510
h
_12
h
: limit_switch_selector
Through the object 6510h_12h (limit_switch_selector), assignment of the limit switches (negative,
positive) can be exchanged without having to make changes to the cabling. To exchange the assign
ment of the limit switches, a One must be entered.
Sub-Index
12
h
Description
limit_switch_selector
Data Type
INT16
Access
rw
PDO mapping
no
Units
–
Value Range
0, 1
Default Value
0
Value
Meaning
0
DIN6 = E0 (limit switch negative)
DIN7 = E1 (limit switch positive)
1
DIN6 = E1 (limit switch positive)
DIN7 = E0 (limit switch negative)
Object 6510
h
_14
h
: homing_switch_polarity
The polarity of the reference switch can be programmed through the object 6510
h
_14
h
(homing_switch_polarity). For a normally closed reference switch, a zero is entered in this object,
whereas a “1” is entered when normally open contacts are used.
Sub-Index
14
h
Description
homing_switch_polarity
Data Type
INT16
Access
rw
PDO mapping
no
Units
–
Value Range
0, 1
Default Value
1
Value
Meaning
0
N/C contact
1
N/O contact