Error group 64
DeviceNet (only CMMP-AS-...-M3)
No.
Reaction
Message
Code
64-3
-
DeviceNet: TX queue overflow
configurable
Cause
Insufficient free space on the CAN bus for sending messages.
Measure
Increase the baud rate.
Reduce the number of nodes.
Reduce the scan rate.
64-4
-
DeviceNet: IO message not sent
configurable
Cause
Error sending I/O data.
Measure
Check that the network is connected correctly and has no
faults.
64-5
-
DeviceNet: Bus OFF
configurable
Cause
The CAN controller is BUS OFF.
Measure
Check that the network is connected correctly and has no
faults.
64-6
-
DeviceNet: CAN controller overflow
configurable
Cause
The CAN controller has an overflow.
Measure
Increase the baud rate.
Reduce the number of nodes.
Reduce the scan rate.
Error group 65
DeviceNet (only CMMP-AS-...-M3)
No.
Code
Message
Reaction
65-0
-
DeviceNet active, but no module
configurable
Cause
The DeviceNet communication is activated in the parameter set of
the motor controller, but no interface is available.
Measure
Deactivate DeviceNet communication.
Connect an interface.
65-1
-
Timeout IO connection
configurable
Cause
Interruption of an I/O connection.
Measure
No I/O message was received within the expected time.
Error group 66
Modbus/TCP
No.
Code
Message
Reaction
66-0
-
Modbus/TCP: No free TCP/IP instances
Warn
Cause
Ethernet stack can download the requested TCP connection does
not provide. Internal device error.
Measure
Restart device or restore factory settings.
If the error occurs lasting effect on the HW is defective. Can not
be repaired on site.