5
Setting parameters
134
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
5.14
Limit Switch/Reference Switch
Overview
Proximity switches (limit switch) or reference switches (homing switch) can be used alternatively for
definition of the reference position of the motor controller. Further information on the possible homing
methods can be found in chapter 7.2, Operating mode reference travel (homing mode).
Description of the objects
Index
Object
Name
Type
Attr.
6510
h
RECORD
drive_data
rw
Object 6510
h
_11h: limit_switch_polarity
The polarity of the limit switches can be programmed via the object 6510h_11h (limit_switch_polarity).
For normally closed limit switches, a “0” must be entered in this object, whereas a “1” must be entered
when normally open contacts are used.
Index
6510
h
Name
drive_data
Object Code
RECORD
No. of Elements
51
Sub-Index
11
h
Description
limit_switch_polarity
Data Type
INT16
Access
rw
PDO mapping
no
Units
–
Value Range
0, 1
Default Value
1
Value
Meaning
0
N/C contact
1
N/O contact