Diagnostic messages
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
253
Error group 42
Positioning
No.
Code
Message
Reaction
42-0
8680h
Positioning: Drive stops automatically because there is no
follow-up positioning
configurable
Cause
The positioning target cannot be reached through the positioning
or edge conditions options.
Measure
Check the parameterisation of the relevant position sets.
42-1
8681h
Positioning: Drive stops as rotation reversal is not allowed
configurable
Cause
The positioning target cannot be reached through the positioning
or edge conditions options.
Measure
Check the parameterisation of the relevant position sets.
42-2
8682h
Positioning: Illegal rotation reversal after "stop"
configurable
Cause
The positioning target cannot be reached through the positioning
or edge conditions options.
Measure
Check the parameterisation of the relevant position sets.
42-3
-
Start positioning rejected: Wrong mode of operation
configurable
Cause
Switching of the operating mode by means of the position record
was not possible.
Measure
Check the parameterisation of the relevant position sets.
42-4
-
Please enforce homing run!
configurable
Cause
A normal position record was started, but the drive needs a valid
reference position before starting.
Measure
Execute new homing.
42-5
-
Rotary axis: Direction of rotation is not allowed
configurable
Cause
–
The positioning target cannot be reached through the position
ing or edge conditions options.
–
The calculated direction of rotation is not permitted for the
modulo positioning in the set mode.
Measure
Check the chosen mode.
42-9
-
Error at starting the positioning
configurable
Cause
–
Acceleration limit value exceeded.
–
Position record blocked.
Measure
Check parameterisation and sequence control, correct if neces
sary.
Error group 43
Hardware limit switch
No.
Code
Message
Reaction
43-0
8081h
Limit switch: Negative setpoint value blocked
configurable
Cause
Negative hardware limit switch reached.
Measure
Check parameterisation, wiring and limit switches.