Setting parameters
132
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Value
Measurement file
0
Off (output is low)
1
Position X
setpoint
= X
dest
2
Position X
act
= X
dest
3
Reserved
4
Remaining path trigger active
5
Reference run active
6
Declared Velocity Reached
7
I
2
t motor reached
8
Contouring error
9
Undervoltage in intermediate circuit
10
Holding brake released
11
Output stage switched on
12
On (output is high)
13
Common error active
14
At least one setpoint lock active
15
Linear motor identified
16
Homing position valid
17
Common status: ready for controller enable
18
Position Trigger 1
19
Position Trigger 2
20
Position Trigger 3
21
Position Trigger 4
22 … 25
Reserved
26
Alternative target reached
27
Active if position set running
28
Declared torque reached
29
Position x_set = x_target (also with linking for at least 10 ms)
30
Ack signal (active low) as handshake to start position
31
Destination reached with handshake for the dig. Start, is not set as long as START is
on HIGH level.
32
Cam disc active
33
CAM-IN movement in operation
34
CAM-CHANGE, like CAM-IN, but change to a new curve
35
CAM-OUT movement in operation
36
Level of digital output stage enable, that is level at DIN4 (high if DIN4 high)
37
Reserved
38
CAM active without CAM-IN or CAM-CHANGE movement
39
Speed actual value in the window for rest
40
Teach acknowledge
41
Saving process (SAVE!, Save Positions) in operation
42
STO active
43
STO is requested
44
Motion Complete (MC)