![Festo CMMP-AS-***-M0 Series Скачать руководство пользователя страница 248](http://html1.mh-extra.com/html/festo/cmmp-as-m0-series/cmmp-as-m0-series_manual_2283119248.webp)
B
Diagnostic messages
248
Festo – GDCP-CMMP-M3/-M0-C-CO-EN – 1510b – English
Error group 31
I²t monitoring
No.
Code
Message
Reaction
31-0
2312h
Motor I²t
configurable
Cause
I²t monitoring of the controller has been triggered.
–
Motor/mechanical system blocked or sluggish.
–
Motor under-sized?
Measure
Check the performance rating of the drive package.
31-1
2311h
Power stage I²t
configurable
Cause
The I²t monitoring is being triggered frequently.
–
Motor controller does not have the required capacity?
–
Mechanical system sluggish?
Measure
Check design of the motor controller,
if necessary use a more powerful type.
Check the mechanical system.
31-2
2313h
PFC I²t
configurable
Cause
PFC power rating exceeded.
Measure
Parameterise operation without PFC (FCT).
31-3
2314h
Braking resistor I²t
configurable
Cause
–
Overloading of the internal braking resistor.
Measure
Use external braking resistor.
Reduce resistance value or use resistor with higher pulse load.
Error group 32
Intermediate circuit fault
No.
Code
Message
Reaction
32-0
3280h
Intermediate circuit charging time exceeded
configurable
Cause
The intermediate circuit could not be charged after the mains
voltage was applied.
–
A fuse may be faulty, or
–
an internal braking resistor may be faulty, or,
–
in the case of operation with an external resistor, that resistor
is not connected.
Measure
Check interface to the external braking resistor.
Alternatively, check whether the jumper for the internal braking
resistor is in place.
If the interface is correct, the internal braking resistor or the built-
in fuse is probably faulty. On-site repair is not possible.
32-1
3281h
Undervoltage for active PFC
configurable
Cause
The PFC cannot be activated at all until an intermediate circuit
voltage of about 130 V DC is reached.
Measure
Check the power supply.